B.3 Parameter Table
400 YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
d: Speed References
Speed Reference parameters are used to set the various speed reference values during operation.
d1: Speed Reference
No.(Addr.) Name Description Setting Page
d1-01
(280H)
Speed Reference 1
Sets the Speed reference for the drive when d1-18 is set to 0 or 3. Setting units are determined
by parameter o1-03.
Default: 0.00%
<6>
Min: 0.00%
Max: 100.00%
<6>
183
d1-02
(281H)
Speed Reference 2 183
d1-03
(282H)
Speed Reference 3 183
d1-04
(283H)
Speed Reference 4 183
d1-05
(284H)
Speed Reference 5 183
d1-06
(285H)
Speed Reference 6 183
d1-07
(286H)
Speed Reference 7 183
d1-08
(287H)
Speed Reference 8 183
d1-18
(2C0H)
Speed Reference Selection Mode
Sets the mode of speed reference selection by digital inputs.
0: Use multi-speed references (d1-01 to d1-08)
1: High speed reference has priority (d1-19 to d1-23, d1-26)
2: Leveling speed reference has priority (d1-19 to d1-23, d1-26)
3: Use multi-speed references d1-02 to d1-08, no speed selection stops the drive. Drive will stop
when all input terminals programmed for speed references (H1- = 3, 4, 5) are open.
Default: 0
Min: 0
Max: 3
183
d1-19
(2C1H)
Nominal Speed
Sets the nominal speed reference when d1-18 = 1 or 2.
Default: 100.00%
<6>
Min: 0.00%
Max: 100.00%
<6>
184
d1-20
(2C2H)
Intermediate Speed 1
Sets intermediate speed reference 1 when d1-18 = 1 or 2.
Default: 0.00%
<6>
Min: 0.00%
Max: 100.00%
<6>
184
d1-21
(2C3H)
Intermediate Speed 2
Sets intermediate speed reference 2 when d1-18 = 1 or 2.
Default: 0.00%
<6>
Min: 0.00%
Max: 100.00%
<6>
184
d1-22
(2C4H)
Intermediate Speed 3
Sets intermediate speed reference 3 when d1-18 = 1 or 3.
Default: 0.00%
<6>
Min: 0.00%
Max: 100.00%
<6>
184
d1-23
(2C5H)
Releveling Speed
Sets speed reference for releveling when d1-18 = 1 or 2.
Default: 0.00%
<6>
Min: 0.00%
Max: 100.00%
<6>
184
d1-24
(2C6H)
Inspection Operation Speed
Sets speed reference when inspection operation is enabled.
Default: 50.00%
<6>
Min: 0.00%
Max: 100.00%
<6>
184
d1-25
(2C7H)
Rescue Operation Speed
Sets the speed reference during inspection operation.
Default: 10.00%
<6>
Min: 0.00%
Max: 100.00%
<6>
184
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly