8.5 Installing Peripheral Devices
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 375
Peripheral Devices &
Options
8
◆ Attachment for External Heatsink Mounting
An external attachment can be used to project the heatsink outside of an enclosure to ensure that there is sufficient air
circulation around the heatsink. Contact a Yaskawa sales representative or Yaskawa directly for more information on this
attachment.
◆ EMC Filter Installation
This drive is tested according to European standards IEC/EN 61800-5-1 and complies with the EMC guidelines. Refer to
EMC Filter Installation on page 477 for details about EMC filter selection and installation.
40031 20 39 75 60 110 FWH-200B (200)
40039 25 47 75 75 125 FWH-250A (250)
40045 30 43 75 75 125 FWH-250A (250)
40060 40 58 100 100 150 FWH-250A (250)
40075 60 71 125 110 200 FWH-250A (250)
40091 60 86 150 150 250 FWH-250A (250)
40112 75 105 175 175 300 FWH-350A (350)
40150 100 142 225 225 400 FWH-400A (400)
40180 125 170 250 250 500 FWH-500A (500)
40216 150 207 350 350 600 FWH-600A (600)
40260 200 248 400 400 700 FWH-700A (700)
40304 250 346 600 600 1000
<5>
FWH-800A (800)
40370 300 410 800 700 1200
<5>
FWH-800A (800)
40450 350 465 900 800 1350
<5>
FWH-1000A (1000)
40605 400-450-500 657 1200 1100
<5>
1800
<5>
FWH-1200A (1200)
Three-Phase 600 V Class
50003 2 3.6 15 6.25 10 FWP-50B (50)
50004 3 5.1 15 8 15 FWP-60B (60)
50006 5 8.3 15 12 20 FWP-60B (60)
50010 7.5 12 20 20 35 FWP-70B (70)
50013 10 16 30 25 45 FWP-100B (100)
50017 15 23 40 40 60 FWP-100B (100)
50022 20 31 60 50 90 FWP-125A (125)
50027 25 38 75 60 100 FWP-125A (125)
50032 25-30 33 60 50 90 FWP-175A (175)
50041 40 44 75 75 125 FWP-175A (175)
50052 50-60 54 100 90 150 FWP-250A (250)
50062 50-60 66 125 110 175 FWP-250A (250)
50077 75 80 150 125 225 FWP-250A (250)
50099 100 108 175 175 300 FWP-350A (350)
50130 125 129 250 225 350 FWP-350A (350)
50172 150 158 300 250 400 FWP-600A (600)
50200 200 228 400 350 600 FWP-600A (600)
<1> Maximum MCCB Rating is 15 A, or 200% of drive input current rating, whichever is larger. MCCB voltage rating must be 600 VAC or greater.
<2> Maximum Time Delay fuse is 175% of drive input current rating. This covers any Class CC, J or T class fuse.
<3> Maximum Non-time Delay fuse is 300% of drive input current rating. This covers any CC, J or T class fuse.
<4> When using semiconductor fuses, Bussmann FWH and FWP are required for UL compliance. Select FWH for 200 V Class and 400 V Class
models and FWP fuses for 600 V models.
<5> Class L fuse is also approved for this rating.
Drive Model
CIMR-LU
L1000A
Nominal Output
Power HP
AC Drive Input
Amps
MCCB Rating
Amps
<1>
Time Delay Fuse
Rating Amps
<2>
Non-time Delay
Fuse Rating Amps
<3>
Bussmann
Semi-conductor Fuse Rating
(Fuse Ampere)
<4>
SIEP_C710616_38F_5_0.book 375 ページ 2015年11月9日 月曜日 午後3時36分