B.3 Parameter Table
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 395
Parameter List
B
b: Application
Application parameters configure the source of the Up/Down command, timer functions, the Dwell function, the Droop
Control function, Energy Savings, and a variety of other application-related settings.
b1: Operation Mode Selection
b2: Magnetic Flux Compensation
b4: Delay Timers
b6: Dwell Function
No.(Addr.) Name Description Setting Page
b1-01
(180H)
Speed Reference Selection
0: Digital operator
1: Analog input terminals
2: MEMOBUS/Modbus communications
3: Option card
Default: 0
Min: 0
Max: 3
166
b1-02
(181H)
Up/Down Command Selection
0: Digital operator
1: Digital input terminals
2: MEMOBUS/Modbus communications
3: Option card
Default: 1
Min: 0
Max: 3
167
b1-03
(182H)
Stopping Method Selection
0: Ramp to stop
1: Coast to stop
4: Elevator Emergency Stop
Note: Setting 4 is available in the control mode CLV or CLV/PM for drives with software
versions PRG: 7017 or later. The setting is 0 or 1 for software version PRG: 7016.
Default: 0
Min: 0
Max: 4
167
b1-06
(185H)
Digital Input Reading
0: Input status is read once and processed immediately (for quick response).
1: Input is read twice and processed only if the status is the same in both readings (robust
against noisy signals).
Default: 1
Min: 0
Max: 1
168
b1-08
(187H)
Up/Down Command Selection
while in Programming Mode
0: Up/Down command not accepted while in the Programming Mode.
1: Up/Down command accepted while in the Programming Mode.
2: Prohibit entering Programming Mode during run.
Default: 0
Min: 0
Max: 2
168
b1-14
(1C3H)
Phase Order Selection
0: U-V-W
1: U-W-V
Default: 0
Min: 0
Max: 1
168
No.(Addr.) Name Description Setting Page
b2-08
(190H)
Magnetic Flux Compensation
Val ue
Sets the magnetic flux compensation as a percentage of the no-load current value (E2-03).
Default: 0%
Min: 0%
Max: 1000%
169
No.(Addr.) Name Description Setting Page
b4-01
(1A3H)
Timer Function On-Delay Time
Used to set the on-delay and off-delay times for a digital timer output (H2- = 12). The
output is triggered by a digital input programmed to H1- = 18).
Default: 0.0 s
Min: 0.0 s
Max: 3000.0 s
169
b4-02
(1A4H)
Timer Function Off-Delay Time
Default: 0.0 s
Min: 0.0 s
Max: 3000.0 s
169
No.(Addr.) Name Description Setting Page
b6-01
(1B6H)
Dwell Speed at Start
Parameters b6-01 and b6-02 set the speed to hold and the time to maintain that speed at start.
Parameters b6-03 and b6-04 set the speed to hold and the time to maintain that speed at stop.
Default: 0.0%
Min: 0.0%
Max: 100.0%
170
b6-02
(1B7H)
Dwell Time at Start
Default: 0.0 s
Min: 0.0 s
Max: 10.0 s
170
b6-03
(1B8H)
Dwell Speed at Stop
Default: 0.0%
Min: 0.0%
Max: 100.0%
170
b6-04
(1B9H)
Dwell Time at Stop
Default: 0.0 s
Min: 0.0 s
Max: 10.0 s
170
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
common_
TMonly
CLV
CLV/PM
V/f OLV
All Modes
common_
TMonly
All Modes
common_
TMonly