C.5 Drive Operations by MEMOBUS/Modbus
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 451
MEMOBUS/Modbus
Communications
C
C.5 Drive Operations by MEMOBUS/Modbus
The drive operations that can be performed by MEMOBUS/Modbus communication depend on drive parameter settings.
This section explains the functions that can be used and related parameter settings.
Observing the Drive Operation
A PLC can perform the following actions with MEMOBUS/Modbus communications at any time regardless of parameter
settings (except H5-).
Observe drive status and drive control terminal status from a PLC.
Read and write parameters.
Set and reset faults.
Set multi-function inputs.
Note: Input settings from the input terminals S and from MEMOBUS/Modbus communications are both linked by a logical OR
operation.
Controlling the Drive
Select an external reference and adjust the parameters in Table C.1 accordingly to start and stop the drive or set the
frequency reference using MEMOBUS/Modbus communications.
Table C.1 Setting Parameters for Drive Control from MEMOBUS/Modbus
Refer to b1-01: Speed Reference Selection on page 166 and Refer to b1-02: Up/Down Command Selection on page 167
for details on operation mode parameter selections.
Reference Source Parameter Name Required Setting
External Reference
b1-01 Speed Reference Selection 2
b1-02 Up/Down command Selection 2