42 YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
2.2 Mechanical Installation
2.2 Mechanical Installation
This section outlines specifications, procedures, and the environment for proper mechanical installation of the drive.
CAUTION! Crush Hazard. Carrying the drive by the front cover may cause the main body of the drive to fall, resulting in minor or
moderate injury. Always hold the case when carrying the drive.
Installation Environment
Install the drive in an environment matching the specifications below to help prolong the optimum performance life of the
drive.
Table 2.1 Installation Environment
NOTICE: Avoid placing drive peripheral devices, transformers, or other electronics near the drive as the noise created can lead to
erroneous operation. If such devices must be used in close proximity to the drive, take proper steps to shield the drive from noise.
NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the drive during installation. Failure to
comply could result in damage to the drive. Place a temporary cover over the top of the drive during installation. Remove the temporary
cover before startup, as the cover will reduce ventilation and cause the drive to overheat.
Environment Conditions
Installation Area Indoors
Ambient Temperature
IP00 enclosure with top protective cover: -10 to +40°C (14 to 104°F)
IP00 enclosure: -10 to +50°C (14 to 122°F)
Drive reliability improves in environments without wide temperature fluctuations.
When using the drive in an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air temperature inside the enclosure
does not exceed the specified levels.
Do not allow ice to develop on the drive.
Humidity 95% RH or less and free of condensation
Storage Temperature -20 to 60°C (-4 to 140°F)
Surrounding Area
Install the drive in an area free from:
oil mist and dust
metal shavings, oil, water or other foreign materials
radioactive materials
combustible materials (e.g., wood)
harmful gases and liquids
excessive vibration
chlorides
direct sunlight
Altitude
1000 m or lower, up to 3000 m with derating 1000 m (3280 ft.) or lower, up to 3000 m (9842 ft.) with derating (Refer to Drive Derating Data on
page 385.)
Vibration
10 to 20 Hz at 9.8 m/s
2
20 to 55 Hz at 5.9 m/s
2
(CIMR-LU20008 to 20180, 40005 to 40150, and 50003 to 50077)
2.0 m/s
2
(CIMR-LU20215 to 20415, CIMR-LU40180 to 40605, and 50099 to 50200)
Orientation Install the drive vertically to maintain maximum cooling effects.