2.2 Mechanical Installation
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 43
◆ Installation Orientation and Spacing
WARNING! Fire Hazard. Provide sufficient cooling when installing the drive inside an enclosed panel or cabinet. Failure to comply
could result in overheating and fire. When drives are placed inside the same enclosure panel, install proper cooling to ensure air
entering the enclosure does not exceed 40
°
C (104
°
F).
■ Installation Orientation
Install the drive upright as illustrated in Figure 2.1 to maintain proper cooling. Refer to Mechanical Installation on
page 42 for details on installing the drive.
Figure 2.1
Figure 2.1 Correct Installation Orientation
■ Installation Spacing
Figure 2.2 shows the installation distance required to maintain sufficient space for airflow and wiring.
Figure 2.2
Figure 2.2 Correct Installation Spacing
A – 50 mm (1.97 in.) minimum C – 120 mm (4.72 in.) minimum
B – 30 mm (1.18 in.) minimum D – Airflow direction
OK Not OK Not OK
A
A
BB
Side Clearance Top/Bottom Clearance
C
C
D
D
SIEP_C710616_38F_5_0.book 43 ページ 2015年11月9日 月曜日 午後3時36分