B.3 Parameter Table
424 YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
◆ S: Elevator Parameters
This section describes various functions and faults needed to operate an elevator application: braking sequence, slip
compensation for elevators, start/stop optimization, Rescue Operation, and elevator-related faults.
■
S1: Brake Sequence
No. (Addr.) Name Description Setting Page
S1-01
(680H)
<5> Default setting is determined by the control mode (A1-02).
<39> Available in drive software versions PRG: 7016 or later.
<44> Available in drive software versions PRG: 7017 or later.
Zero Speed Level at Stop
Determines the speed to begin applying DC Injection (or Position Lock) when the drive is
ramping to stop (b1-03 = 0). Set as a percentage of the maximum output frequency (E1-04).
Default:
<5>
Min: 0.000%
Max: 9.999%
258
S1-02
(681H)
DC Injection Current at Start
Determines the amount of current to use for DC Injection at start. Set as a percentage of the
drive rated current.
Default: 50%
Min: 0%
Max: 100%
258
S1-03
(682H)
DC Injection Current at Stop
Determines the amount of current to use for DC Injection at stop. Set as a percentage of the
drive rated current.
Default: 50%
Min: 0%
Max: 100%
258
S1-04
(683H)
DC Injection/Position Lock Time
at Start
Determines how long the drive should perform DC Injection at start. In CLV and CLV/PM,
S1-04 determines how long Position Lock should be performed. A setting of 0.00 disables
S1-04.
Default: 0.40 s
Min: 0.00 s
Max: 10.00 s
258
S1-05
(684H)
DC Injection/Position Lock Time
at Stop
Determines how long the drive should perform DC Injection at stop. In CLV and CLV/PM,
S1-05 determines how long Position Lock should be performed. A setting of 0.00 disables
S1-05.
Default: 0.60 s
Min: 0.00 s
Max: 10.00 s
259
S1-06
(685H)
Brake Release Delay Time
Determines the delay time between the start of DC injection/Position Lock and setting the brake
control command (H2- = 50) in order to release the brake at the beginning of the ride.
Default: 0.20 s
Min: 0.00 s
Max: 10.00 s
259
S1-07
(686H)
Brake Close Delay Time
Determines the delay time between reaching Zero Speed (S1-01) and resetting the brake control
command (H2- = 50) in order to apply the brake at the end of the ride.
Default: 0.10 s
Min: 0.00 s
Max: [S1-05]
259
S1-10
(687H)
Run Command Delay Time
Sets the time that must pass after the Up/Down command is entered until the drive internal Run
command is set and the ride is started.
Default: 0.10 s
Min: 0.00 s
Max: 1.00 s
259
S1-11
(688H)
Output Contactor Open Delay
Time
Determines the delay time between shutting off the output of the drive and resetting the
contactor control command (H2- = 51) in order to release the motor contactor after a ride
has finished.
Default: 0.10 s
Min: 0.00 s
Max: 1.00 s
259
S1-12
(6E0H)
<39>
Motor Contactor Control During
Auto-Tuning
Determines the state of the output contactor control command (H2- = 51) during
Auto-Tuning.
0: Disabled
1: Enabled
2: Enabled during Auto-Tuning and HBB
Note: Setting 2 is available in the control mode CLV or CLV/PM for drives with software
versions PRG: 7017 or later. The setting is 0 or 1 for software version PRG: 7016.
Default: 0
Min: 0
Max: 2
259
S1-26
(6D7H)
<44>
Emergency Stop Start Level
Sets the Emergency Stop Start Level as a percentage of the Maximum Output Frequency.
Default: 10.0%
Min: 0.0%
Max: 100.0%
260
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes