84 YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
3.9 Control I/O Configuration
3.9 Control I/O Configuration
Setting Sink/Source with Input Terminals SN and SP
Note: Terminals H1, H2, DM+, and DM- on 600 V class models are designed to the functionality, but are not certified to IEC/EN
61800-5-2, ISO/EN 13849 Cat.3, IEC/EN 61508 SIL2, Insulation coordination: class 1.
Use the wire jumper between terminals SC and SP or SC and SN to select between Sink mode, Source mode or external
power supply for the digital inputs S1 to S8 as shown in Table 3.11 (Default: Sink mode, internal power supply).
NOTICE: Damage to Equipment. Do not short terminals SP and SN. Failure to comply will damage the drive.
Table 3.11 Digital Input Sink / Source / External Power Supply Selection
Drive Internal Power Supply (Terminal SN and SP) External 24 Vdc Power Supply
Sinking Mode (NPN)
Sourcing Mode (PNP)
SC
S8
S7
24 Vdc
SP
SN
SC
S8
S7
24
Vdc
SP
SN
External
24
Vdc
±
10%
SC
S8
S7
24 Vdc
SP
SN
SC
S8
S7
24
Vdc
SP
SN
External
24
Vdc
±
10%