5.6 F: Option Settings
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 201
◆ F6: Communication Option Card
These parameters configure communication option cards and communication fault detection methods.
■
F6-01: Operation Selection after Communications Error
Determines drive operation when a communication error occurs.
Setting 0: Ramp to stop (uses the deceleration ramp set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop ramp set to C1-09)
Setting 3: Alarm only (continue operation)
■ F6-02: External Fault from Communication Option Detection Selection
Determines the detection method of an external fault (EF0) initiated by a communication option card.
Setting 0: Always detected
Setting 1: Detection during run only
■ F6-03: External Fault from Communication Option Operation Selection
Determines drive operation when an external fault is initiated by a communication option (EF0).
Setting 0: Ramp to stop (uses the deceleration ramp set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop ramp set to C1-09)
Setting 3: Alarm only (continue operation)
■ F6-04: bUS Error Detection Time
Sets the delay time for bUS error detection.
■
F6-06: Torque Limit Selection from Communications Option
Selects whether torque limit values are assigned to the drive from the network.
Setting 0: Disabled
Setting 1: Enabled
No. Parameter Name Setting Range Default
F6-01
Operation Selection after Communications Error
0 to 3 1
No. Parameter Name Setting Range Default
F6-02 External Fault from Communication Option Detection Selection 0 or 1 0
No. Parameter Name Setting Range Default
F6-03 External Fault from Communication Option Operation Selection 0 to 3 1
No. Parameter Name Setting Range Default
F6-04
bUS Error Detection Time
0.0 to 5.0 s 2.0 s
No. Parameter Name Setting Range Default
F6-06
Torque Limit Selection from Communications Option
0, 1 0