5.11 S: Elevator Parameters
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 273
Parameter Details
5
S6: Faults for Elevator Applications
S6-01: Motor Contactor Response Error (SE1) Detection/Reset Selection
Determines when the drive should detect a motor contactor response error (SE1). SE1 is triggered if there is no response
from the motor contactor within the time set in S6-10 after the contactor control output has been set.
Setting 0: Detect during stop, SE1 must be manually reset
Setting 1: Detect during stop, SE1 can be automatically reset
Setting 2: No SE1 detection
S6-02: Starting Current Error (SE2) Detection Delay Time
Sets a delay time for starting current error (SE2). SE2 is detected when the drive output current is below 25% after the
Up/Down command has been entered and the brake release time and the time set to S6-02 have both passed. The brake
control command will not be issued (brake stays applied).
S6-03: SE2 Detect Current Level
Note: Available in drive software PRG: 7017 or later.
Sets the level of current applied to the motor when the Brake Control command is activated, as a percentage of the Motor
No-load Current (E2-03). A Starting Current Error (SE2) occurs when the drive’s output current is less than the value in
S6-03 after both the Brake Release Delay Time (S1-06) and the SE2 Detection Delay Time (S6-02) have passed after a
RUN command.
S6-04: Output Current Error (SE3) Detection Delay Time
Sets a delay time for detecting an output current fault (SE3). SE3 is detected when the drive output current drops below
25% after the brake has released.
S6-05: Brake Response Error (SE4) Detection Time
Sets a delay time for detecting a brake response error (SE4). SE4 is detected when an output terminal set for “Brake
release” (H2- = 50) and an input terminal set for “Brake feedback” (H1- = 79) do not match for the time set to
S6-05.
No. Parameter Name Setting Range Default
S6-01 Motor Contactor Response Error (SE1) Detection/Reset Selection 0 to 2 0
No. Parameter Name Setting Range Default
S6-02 Starting Current Error (SE2) Detection Delay Time 0.00 to [S1-04 – S1-06] 200 ms
No. Parameter Name Setting Range Default
S6-03 SE2 Detect Current Level 0 to 100% 25%
No. Parameter Name Setting Range Default
S6-04 Output Current Error (SE3) Detection Delay Time 0 to 5000 ms 200 ms
No. Parameter Name Setting Range Default
S6-05 Brake Response Error (SE4) Detection Time 0 to 10000 ms 500 ms