EasyManua.ls Logo

YASKAWA L1000A - D.2 European Standards

YASKAWA L1000A
522 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
474 YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
D.2 European Standards
D.2 European Standards
Figure D.1
Figure D.1 CE Mark
The CE mark indicates that a product is in compliance with applicable European Directives for safety and environmental
regulations. It is required for engaging in business and commerce in Europe.
The applicable European Directives for this product are as follows. We declared the CE marking based on the harmonized
standards in the following table.
The user(s) is solely responsible for ensuring that the end products used with this drive comply with all applicable
European directives and with other national regulations (if required).
Note: 600 V class drives (models 5) are not compliant with European Standards.
CE Low Voltage Directive Compliance
This drive has been tested according to European standard IEC/EN 61800-5-1, and it fully complies with the Low Voltage
Directive.
To comply with the Low Voltage Directive, be sure to meet the following conditions when combining this drive with
other devices:
Area of Use
Do not use drives in areas with pollution higher than degree 2 and overvoltage category 3 in accordance with IEC/EN
664.
Factory Recommended Branch Circuit Protection
Table D.1 Recommended Input Fuse Selection
Applicable European Directive
<1> These standards are in compliance for models CIMR-LF only.
Applicable Harmonized Standards
Low Voltage Directive (2006/95/EC) IEC/EN 61800-5-1: 2007
EMC Directive (2004/108/EC)
EN 61800-3: 2004/A1: 2012
IEC 61800-3: 2004/A1: 2011
Machinery Directive (2006/42/EC)
ISO/EN ISO 13849-1/AC: 2009
<1>
IEC/EN 62061: 2005 (SILCL3)
<1>
IEC/EN 61800-5-2: 2007 (SIL3)
<1>
Drive Model
CIMR-LU
L1000
Nominal Output
Power HP
AC Drive Input
Amps
MCCB Rating
Amps
<1>
Time Delay Fuse
Rating Amps
<2>
Non-time Delay
Fuse Rating Amps
<3>
Bussmann
Semi-conductor Fuse Rating
(Fuse Ampere)
<4>
Three-Phase 200 V Class
20008 2 7.5 15 12 20 FWH-70B (70)
20011 3 11 20 17.5 30 FWH-70B (70)
20014 3 15.6 25 25 40 FWH-90B (90)
20018 5 18.9 35 30 50 FWH-90B (90)
20025 7.5 28 50 40 75 FWH-100B (100)
20033 10 37 60 60 100 FWH-200B (200)
20047 15 52 100 90 150 FWH-200B (200)
20060 20 68 125 110 200 FWH-200B (200)
20075 25 80 150 125 225 FWH-300A (300)
20085 30 82 150 125 225 FWH-300A (300)
20115 40 111 200 175 250 FWH-350A (350)
SIEP_C710616_38F_5_0.book 474 ージ 015年11月9日 月曜日 午後3時36分