5.10 o: Operator Related Settings
254 YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
■ o2-06: Operation Selection when Digital Operator is Disconnected
Determines whether the drive will stop when the digital operator is removed in LOCAL mode or when b1-02 is set to 0.
When the operator is reconnected, the display will indicate that it was disconnected.
Setting 0: Continue operation
The operation is continued.
Setting 1: Trigger a fault
The operation is stopped and an “oPr” fault is triggered. The motor coasts to stop.
◆ o3: Copy Function
These parameters control the Copy function of the digital operator. The Copy function stores parameter settings into the
memory of the digital operator to facilitate the transfer of those settings to other drives that are the same model, capacity,
and same control mode setting. Refer to Copy Function Related Displays on page 311 for a description of errors and
displays.
■
o3-01 Copy Function Selection
Instructs the drive to Read, Write, or Verify parameter settings.
Setting 0: Copy Select (no function)
Setting 1: INV → OP READ
Copies all parameters from the drive to the digital operator.
Note: The copy protection for the digital operator is enabled by default. Set o3-02 to 1 to unlock copy protection.
Setting 2: OP → INV WRITE
Compares the parameters in the drive with the parameter settings saved on the digital operator for matches.
Setting 3: OP ↔ INV VERIFY
Parameters in the drive are compared with the parameter settings saved on the digital operator to see if they match.
■
o3-02 Copy Allowed Selection
Allows and restricts the use of the Copy function.
Setting 0: Disabled
Setting 1: Enabled
No. Parameter Name Setting Range Default
o2-06 Digital Operator Disconnection Operation 0 or 1 0
No. Parameter Name Setting Range Default
o3-01 Copy Function Selection 0 to 3 0
No. Parameter Name Setting Range Default
o3-02 Copy Allowed Selection 0 or 1 0