394 YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
B.3 Parameter Table
B.3 Parameter Table
A: Initialization Parameters
The A parameter group creates the operating environment for the drive. This includes the parameter Access Level, Motor
Control Method, Password, User Parameters and more.
A1: Initialization Parameters
A2: User Parameters
No.(Addr.) Name Description Setting Page
A1-00
(100H)
<1>
<1> Parameter setting value is not reset to the default value when the drive is initialized.
Language Selection
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
7: Chinese
8: Czech
9: Russian
10: Turkish
11: Polish
12: Greek
Note: 1. Language selection settings 8 to 12 can be selected from an LCD operator with version
(REV) F or later. The version number of the LCD operator's PRG software is shown on
the back of the digital operator.
2. Language selection settings 8 to 12 are available in drive software PRG: 7017 or later.
Default: 0
Min: 0
Max: 12
160
A1-01
(101H)
Access Level Selection
0: View and set A1-01 and A1-04. U- parameters can also be viewed.
1: User Parameters (access to a set of parameters selected by the user, A2-01 to A2-32)
2: Advanced Access (access to view and set all parameters)
Default: 2
Min: 0
Max: 2
160
A1-02
(102H)
<1>
Control Method Selection
0: V/f Control
2: Open Loop Vector Control
3: Closed Loop Vector Control
7: Closed Loop Vector Control for PM Motors
Default: 2
Min: 0
Max: 7
161
A1-03
(103H)
Initialize Parameters
0: No initialization
1110: User Initialize (parameter values must be stored using parameter o2-03)
2220: 2-wire initialization
5550: oPE04 error reset
Default: 0
Min: 0
Max: 5550
161
A1-04
(104H)
Password
When the value set into A1-04 does not match the value set into A1-05, parameters A1-01
through A1-03, and A2-01 through A2-33 cannot be changed.
Default: 0000
Min: 0000
Max: 9999
162
A1-05
(105H)
Password Setting
No.(Addr.) Name Description Setting Page
A2-01 to
A2-32
(106 to 125H)
<5> Default setting is determined by the control mode (A1-02).
User Parameters 1 to 32
Parameters that were recently edited are listed here. The user can also select parameters to
appear here for quick access.
Default:
<5>
Min: A1-00
Max: S6-16
165
A2-33
(126H)
User Parameter Automatic
Selection
0: Parameters A2-01 through A2-32 are reserved for the user to create a list of User Parameters.
1: Save history of recently viewed parameters. Recently edited parameters will be saved to
A2-17 through A2-32 for quick access.
Default: 1
Min: 0
Max: 1
165
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
SIEP_C710616_38F_5_0.book 394 ージ 015年11月9日 月曜日 午後3時36分