5.6 F: Option Settings
200 YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Using Gain and Bias to Adjust Output Signal Level
The output signal is adjustable while the drive is stopped.
Termina l V1
1.
View the value set to F4-02 (Terminal V1 Monitor Gain) on the digital operator. A voltage equal to 100% of the
parameter being set in F4-01 is output at terminal V1.
2. Adjust F4-02 while viewing the monitor connected to the terminal V1.
3. View the value set to F4-05 on the digital operator. Terminal V1 outputs a voltage equal to 0% of the monitor
selected by the setting value of F4-01.
4. Adjust F4-05 while viewing the output signal on the terminal V1.
Termina l V2
1.
View the value set to F4-02 (Terminal V2 Monitor Gain) on the digital operator. A voltage equal to 100% of the
parameter being viewed in F4-03 is output at terminal V2.
2. Adjust F4-04 while viewing the monitor connected to the terminal V2.
3. View the value set to F4-06 on the digital operator. Terminal V2 will output a voltage equal to 0% of the monitor
selected by the setting value of F4-03.
4. Adjust F4-06 while viewing the output signal on the terminal V2.
■ F4-07, F4-08: Terminal V1, V2 Signal Level Selection
Sets the output signal level for terminals V1 and V2.
Setting 0: 0 to 10 V
Setting 1: -10 to 10 V
◆ F5: Digital Output Card Settings
These parameters set up the drive for operation with the digital output option card DO-A3. Refer to the instruction manual
packaged with the option card for specific details on installation, wiring, input signal level selection, and parameter setup.
■
F5-01 through F5-08: Digital Output Option Card Terminal Function Selection
When F5-09 = 2, the parameters listed in the table below are used to assign functions to the output terminals on the option
card.
■
F5-09: DO-A3 Output Mode Selection
Determines how the DO-A3 option card works with the drive.
Setting 0: Separate output functions for each of 8 terminals
Setting 1: Binary output
Setting 2: Output functions assigned by F5-01 through F5-08
No. Parameter Name Setting Range Default
F4-07 Terminal V1 Signal Level Selection 0, 1 1
F4-08 Terminal V2 Signal Level Selection 0, 1 1
No. Parameter Name Setting Range Default
F5-01 Terminal P1-C1 Output Selection 0 to 161 0: During run
F5-02 Terminal P2-C2 Output Selection 0 to 161 1: Zero speed
F5-03 Terminal P3-C3 Output Selection 0 to 161 2: Speed agree 1
F5-04 Terminal P4-C4 Output Selection 0 to 161 4: Speed detection 1
F5-05 Terminal P5-C5 Output Selection 0 to 161 6: Drive ready (READY)
F5-06 Terminal P6-C6 Output Selection 0 to 161 37: During frequency output
F5-07 Terminal M1-M2 Output Selection 0 to 161 F: Not used
F5-08 Terminal M3-M4 Output Selection 0 to 161 F: Not used
No. Parameter Name Setting Range Default
F5-09 DO-A3 Output Mode Selection 0 to 2 0
SIEP_C710616_38F_5_0.book 200 ページ 2015年11月9日 月曜日 午後3時36分