D.3 UL and CSA Standards
488 YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Note: Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum
allowable temperature of 75°C (167°F) 600 Vac UL-approved vinyl-sheathed insulation.
Installing Input Fuses
NOTICE: If a fuse is blown or a Ground Fault Circuit Interrupter (GFCI) is tripped, check the wiring and the selection of the peripheral
devices to identify the cause. Contact Yaskawa before restarting the drive or the peripheral devices if the cause cannot be identified.
Factory Recommended Branch Circuit Protection
Yaskawa recommends installing one of the following types of branch circuit protection to maintain compliance with
UL508C. Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed in
Table D.8.
Table D.8 Factory Recommended L1000A AC Drive Branch Circuit Protection
400 kcmil × 2P M12 200-L12 YF-1, YET-300-1 TD-327, TD-314 TP-200 100-051-564
500 kcmil
600 / 650 kcmil
500 kcmil × 2P
600 kcmil × 2P
M10 325-10 YF-1, YET-300-1 TD-328, TD-315 TP-325 100-051-565
M12 325-12 YF-1, YET-300-1 TD-328, TD-315 TP-325 100-051-277
<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.
Example 1: Models with 300 kcmil for both input and output require one set for input terminals and one set for output terminals, so the user
should order two sets of [100-051-272].
Example 2: Models with 4/0 AWG × 2P for both input and output require two sets for input terminals and two sets for output terminals, so the
user should order four sets of [100-051-560].
Drive Model
CIMR-LU
L1000A in Heavy Duty Mode (C6-01 = 0)
Nominal
Output Power
HP
AC Drive Input Amps
MCCB Rating
Amps
<1>
Time Delay Fuse
Rating Amps
<2>
Non-time Delay Fuse
Rating Amps
<3>
Bussmann
Semiconductor Fuse
Rating (Fuse
Ampere)
<4>
Three-Phase 200 V Class
20008 2 7.5 15 12 20 FWH-70B (70)
20011 3 11 2017.530FWH-70B (70)
20018 5 18.9 35 30 50 FWH-90B(90)
20025 7.5 28 50 40 75 FWH-100B (100)
20033 10 37 60 60 100 FWH-200B (200)
20047 15 52 100 90 150 FWH-200B (200)
20060 20 68 125 110 200 FWH-200B (200)
20075 25 80 150 125 225 FWH-300A (300)
20085 30 82 150 125 225 FWH-300A (300)
20115 40 111 200 175 250 FWH-350A (350)
20145 50 136 250 225 350 FWH-400A (400)
20180 60 164 300 250 450 FWH-400A (400)
20215 75 200 400 350 600 FWH-600A (600)
20283 100 271 500 450 800 FWH-700A (700)
20346 125 324 600 500 900
<4>
FWH-800A (800)
20415 150 394 700 600 1100
<4>
FWH-1000A (1000)
Three-Phase 400 V Class
40005 3 4.4 15 7 12 FWH-70B (70)
40006 3 6 15 10 17.5 FWH-70B (70)
40009 5 10.4 20 17.5 30 FWH-90B (90)
40015 7.5 - 10 15 30 25 40 FWH-80B (80)
40018 10 20 40 35 60 FWH-100B (100)
40024 15 29 50 50 80 FWH-125B (125)
40031 20 39 75 60 110 FWH-200B (200)
40039 25 - 30 47 75 75 125 FWH-250A (250)
40045 30 43 75 75 125 FWH-250A (250)
40060 40 58 100 100 150 FWH-250A (250)
40075 60 71 125 110 200 FWH-250A (250)
40091 60 86 150 150 250 FWH-250A (250)
40112 75 105 175 175 300 FWH-350A (350)
Wire Gauge Terminal Screws
Crimp Terminal
Model Number
Tool
Insulation Cap
Model No.
Code
<1>
Machine No. Die Jaw
SIEP_C710616_38F_5_0.book 488 ージ 015年11月9日 月曜日 午後3時36分