5.6 F: Option Settings
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 199
Parameter Details
5
Setting 0: BCD, 1% units
Setting 1: BCD, 0.1% units
Setting 2: BCD, 0.01% units
Setting 3: BCD, 1 Hz units
Setting 4: BCD, 0.1 Hz units
Setting 5: BCD, 0.01 Hz units
Setting 6: BCD, special setting (5 digit input), 0.02 Hz units
Setting 7: Binary
The unit and the setting range are determined by F3-03.
F3-03 = 0: 255/100% (-255 to +255)
F3-03 = 1: 4095/100% (-4095 to +4095)
F3-03 = 2: 30000/100% (-33000 to +33000)
Note: BCD input when o1-03 = 2 or 3. Units are determined by o1-03.
F3-03: DI-A3 Option Card Data Length Selection
Determines the number of bits for the option card input that sets the speed reference.
Setting 0: 8 bit
Setting 1: 12 bit
Setting 2: 16 bit
F4: Analog Monitor Card Settings
These parameters set up the drive for operation with the analog output option card AO-A3. Refer to the instruction
manual packaged with the option card for specific details on installation, wiring, input signal level selection, and
parameter setup.
F4-01, F4-03: Terminal V1, V2 Function Selection
Selects the data to output from analog terminal V1. Enter the final three digits of U- to determine which monitor
data is output from the option card. Some monitors are only available in certain control modes.
F4-02, F4-04, F4-05, F4-06: Terminal V1, V2 Gain and Bias
Parameters F4-02 and F4-04 determine the gain, while parameters F4-05 and F4-06 set the bias. These parameters are set
as a percentage of the output signal from V1 and V2 where 100% equals 10 V output. The terminal output voltage is
limited to 10 V.
No. Parameter Name Setting Range Default
F3-03
DI-A3 Option Card Data Length Selection
0 to 2 2
No. Parameter Name Setting Range Default
F4-01 Terminal V1 Function Selection 000 to 999 102
F4-03 Terminal V2 Function Selection 000 to 999 103
No. Parameter Name Setting Range Default
F4-02 Terminal V1 Gain -999.9 to 999.9% 100.0%
F4-04 Terminal V2 Gain -999.9 to 999.9% 50.0%
F4-05 Terminal V1 Bias -999.9 to 999.9% 0.0%
F4-06 Terminal V2 Bias -999.9 to 999.9% 0.0%