B.3 Parameter Table
428 YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
■ S6: Error Detection
◆ T: Motor Tuning
Enter data into the following parameters to tune the motor and drive for optimal performance.
■
T1: Induction Motor Auto-Tuning
No. (Addr.) Name Description Setting Page
S6-01
(6B3H)
<7> Default setting value is determined by the digital operator display unit selection (o1-03). The default is normally 1.5 m/s
2
, but when o1-03 = 6,
the default becomes 5.0 ft/s
2
(Setting Range: 0.0 to 50.0 ft/s
2
).
<44> Available in drive software versions PRG: 7017 or later.
Motor Contactor Response Error
(SE1) Detection/Reset Selection
0: Detect during stop, SE1 must be manually reset
1: Detect during stop, SE1 can be automatically reset
2: No SE1 detection
Default: 0
Min: 0
Max: 2
273
S6-02
(6B4H)
Starting Current Error (SE2)
Detection Delay Time
Sets a delay time for detecting SE2.
Default: 200 ms
Min: 0.00 ms
Max: [S1-04]-[S1-06]
273
S6-03
(6B5H)
<44>
SE2 Detect Current Level
Sets the level of current applied to the motor when the Brake Control command is activated, as
a percentage of the Motor No-load Current (E2-03).
Default: 25%
Min: 0%
Max: 100%
273
S6-04
(6B6H)
Output Current Error (SE3)
Detection Delay Time
Sets a delay time for detecting SE3.
Default: 200 ms
Min: 0 ms
Max: 5000 ms
273
S6-05
(6B7H)
Brake Response Error (SE4)
Detection Time
Sets a delay time for detecting SE4.
Default: 500 ms
Min: 0 ms
Max: 10000 ms
273
S6-10
(6B8H)
Overacceleration Detection Level
If the elevator car accelerates at an abnormal rate, the drive triggers an overspeed fault (dv6)
and has the motor coast to stop. Parameter S6-10 determines the acceleration rate that triggers a
fault.
Default:
<7>
Min: 0.0 m/s
2
Max: 20.0 m/s
2
<7>
274
S6-11
(6B9H)
Overacceleration Detection Time
Sets a primary delay for detecting overacceleration.
Default: 50 ms
Min: 0 ms
Max: 5000 ms
274
S6-12
(6BAH)
Overacceleration Detection
Selection
0: Always enabled
1: During run only
Default: 0
Min: 0
Max: 1
274
S6-15
(6BBH)
Speed Reference Loss Detection Enabled or disables detection for speed reference missing (FrL).
0: Disabled
1: Enabled
Default: 1
Min: 0
Max: 1
274
S6-16
(6BCH)
Restart after Baseblock Selection
0: No restart after Baseblock/Safe Torque-Off
1: Restart after Baseblock/Safe Torque-Off
Default: 0
Min: 0
Max: 1
274
No. (Addr.) Name Description Setting Page
T1-01
(701H)
Auto-Tuning Mode Selection
0: Rotational Auto-Tuning
1: Stationary Auto-Tuning 1
2: Stationary Auto-Tuning for Line-to-Line Resistance
4: Stationary Auto-Tuning 2
Default: 0
<5>
Min: 0
Max: 4
<18>
118
T1-02
(702H)
Motor Rated Power
Sets the motor rated power as specified on the motor nameplate.
Note: Use the following formula to convert horsepower into kilowatts: kW = HP × 0.746.
Default:
<4>
Min: 0.00 kW
Max: 650.00 kW
118
T1-03
(703H)
Motor Rated Voltage
Sets the motor rated voltage as specified on the motor nameplate.
Default: 200.0 V
<9>
Min: 0.0 V
Max: 255.0 V
<9>
118
T1-04
(704H)
Motor Rated Current
Sets the motor rated current as specified on the motor nameplate.
Default:
<4>
Min: 10% of drive rated
current
Max: 200% of drive
rated current
<10>
119
All Modes
All Modes
All Modes
All Modes
SIEP_C710616_38F_5_0.book 428 ページ 2015年11月9日 月曜日 午後3時36分