B.3 Parameter Table
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 405
◆ F: Option Settings
F parameters are used to program the drive for Encoder and PG feedback from the motor and to function with option
cards.
■
F1: PG Speed Control Card
No.(Addr.) Name Description Setting Page
F1-01
(380H)
Encoder 1 Resolution
Sets the encoder resolution (number of pulses per revolution)
Default:
<5>
Min: 1 ppr
Max: 60000 ppr
<34>
195
F1-02
(381H)
Operation Selection at PG Open
Circuit (PGo)
0: Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only.
Default: 1
Min: 0
Max: 3
195
F1-03
(382H)
Operation Selection at Overspeed
(oS)
0: Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only.
Default: 1
Min: 0
Max: 3
195
F1-04
(383H)
Operation Selection at Deviation
0: Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only.
Default: 3
Min: 0
Max: 3
196
F1-05
(384H)
Encoder 1 Rotation Direction
Selection 0: A phase leads B in the up direction
1: B phase leads A in the up direction
Default:
<5>
Min: 0
Max: 1
196
F1-06
(385H)
PG 1 Pulse Monitor Output
Division Ratio
Sets the division ratio for the pulse monitor used of the PG option card installed to connector
CN5-C. By setting “xyz”, the division ratio becomes = [(1 + x) / yz]. If only using the A pulse
for one track input, then the input ratio will be 1:1, regardless of what F1-06 is set to.
Default: 1
Min: 1
Max: 132
196
F1-08
(387H)
Overspeed Detection Level
Sets the overspeed detection level as a percentage of the maximum output frequency.
Default: 115%
Min: 0%
Max: 120%
195
F1-09
(388H)
Overspeed Detection Delay Time
Sets the time in seconds for an overspeed situation to trigger a fault (oS).
Default: 0.0 s
Min: 0.0 s
Max: 2.0 s
195
F1-10
(389H)
Excessive Speed Deviation
Detection Level
Sets the speed deviation detection level as a percentage of the maximum output frequency.
Default: 10%
Min: 0%
Max: 50%
196
F1-11
(38AH)
Excessive Speed Deviation
Detection Delay Time
Sets the time in seconds for a speed deviation situation to trigger a fault (dEv).
Default: 0.5 s
Min: 0.0 s
Max: 10.0 s
196
F1-14
(38DH)
PG Open-Circuit Detection Time
Sets the time required to trigger a PG Open fault (PGo).
Default: 2.0 s
Min: 0.0 s
Max: 10.0 s
195
F1-18
(3ADH)
dv3 Detection Selection
0: Disabled
n: Sets the number of dv3 situations that may be detected before triggering an actual dv3 fault.
Default: 10
Min: 0
Max: 10
196
F1-19
(3AEH)
dv4 Detection Selection
0: Disabled
n: Number of pulses that the A and B pulse are reversed that triggers dv4 detection.
Default: 128
Min: 0
Max: 5000
197
F1-20
(3B4H)
PG Option Card Disconnect
Detection 1
0: Disabled
1: Enabled
Default: 1
Min: 0
Max: 1
197
F1-29
(3BFH)
dEv Detection Condition Selection
Selects when DEV is active.
0: After speed reference, soft starter output and motor speed have matched once.
1: After speed reference and soft starter output have matched once.
2: Always during Run
Default: 2
Min: 0
Ma
x: 2
197
CLV
CLV/PM
V/f OLV
CLV
CLV/PM
V/f OLV
CLV
CLV/PM
V/f OLV
CLV
CLV/PM
V/f OLV
CLV
CLV/PM
V/f OLV
CLV
CLV/PM
V/f OLV
CLV
CLV/PM
V/f OLV
CLV
CLV/PM
V/f OLV
CLV
CLV/PM
V/f OLV
CLV
CLV/PM
V/f OLV
CLV
CLV/PM
V/f OLV
CLV
CLV/PM
V/f OLV
CLV
CLV/PM
V/f OLV
CLV
CLV/PM
V/f OLV
CLV
CLV/PM
V/f OLV
SIEP_C710616_38F_5_0.book 405 ページ 2015年11月9日 月曜日 午後3時36分