B.3 Parameter Table
406 YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
■ F3: Digital Input Card (DI-A3)
■ F4: Analog Monitor Card (AO-A3)
F1-50
(3D2H)
<39>
Encoder Selection
Selects the encoder connected the PG-F3 option.
0: EnDat 2.1/01, 2.2/01 Serial Communication + Sin/Cos
1: EnDat 2.2/22 Serial Communication
2: HIPERFACE
Default: 0
Min: 0
Max: 2
197
F1-51
(3D3H)
PGoH Detection Level
Sets the level for detecting PG Hardware Fault (PGoH). Available when F1-20 = 1
Default: 80%
Min: 1%
Max: 100%
198
F1-52
(3D4H)
<39>
Communication Speed of Serial
Encoder Selection
Selects the communication speed between the PG-F3 option and serial encoder.
0: 1M bps/9600 bps
1: 500k bps/19200 bps
2: 1M bps/38400 bps
3: 1M bps/38400 bps
Default: 0
Min: 0
Max: 3
198
F1-63
(2DFH)
PG-E3 R Track Selection
0: Disabled
1: Enabled
Default: 0
Min: 0
Max: 1
198
F1-66 to
F1-81
(B9AH to
BA9H)
<44>
Encoder Adjust 1 to 16
Sets encoder offsets 1 to 16 for the PG-E3 option card. These parameters are automatically set
by the execution of Auto-Tuning of PG-E3 encoder characteristics.
Default: 0
Min: 0
Max: FFFF
198
<5> Default setting is determined by the control mode (A1-02).
<34> Setting range is 1 to 15000 ppr when the drive is set for CLV/PM.
<39> Available in drive software versions PRG: 7016 or later.
<44> Available in drive software versions PRG: 7017 or later.
No.(Addr.) Name Description Setting Page
F3-01
(390H)
DI-A3 Option Card Input Selection
0: BCD, 1% units
1: BCD, 0.1% units
2: BCD, 0.01% units
3: BCD, 1 Hz units
4: BCD, 0.1 Hz units
5: BCD, 0.01 Hz units
6: BCD customized setting (5 digit), 0.02 Hz units
7: Binary input
The unit and the setting range are determined by F3-03.
F3-03 = 0: 255/100% (-255 to +255)
F3-03 = 1: 40961/100% (-4095 to +4095)
F3-03 = 2: 30000/100% (-33000 to +33000)
When the digital operator units are set to be displayed in Hertz or user-set units (o1-03 = 2 or 3),
the units for F3-01 are determined by parameter o1-03.
Default: 0
Min: 0
Max: 7
198
F3-03
(3B9H)
DI-A3 Option Card Data Length
Selection
0: 8 bit
1: 12 bit
2: 16 bit
Default: 2
Min: 0
Max: 2
199
No.(Addr.) Name Description Setting Page
F4-01
(391H)
Terminal V1 Function Selection
Sets the monitor signal for output from terminal V1. Set this parameter to the last three digits of
the desired U- monitor. Some U parameters are available only in certain control modes.
Default: 102
Min: 000
Max: 999
199
F4-02
(392H)
Terminal V1 Gain
Sets the gain for voltage output via terminal V1.
Default: 100.0%
Min: -999.9%
Max: 999.9%
199
F4-03
(393H)
Terminal V2 Function Selection
Sets the monitor signal for output from terminal V2. Set this parameter to the last three digits of
the desired U- monitor. Some U parameters are available only in certain control modes.
Default: 103
Min: 000
Max: 999
199
F4-04
(394H)
Terminal V2 Gain
Sets the gain for voltage output via terminal V2.
Default: 50.0%
Min: -999.9%
Max: 999.9%
199
No.(Addr.) Name Description Setting Page
All Modes
All Modes
All Modes
All Modes
All Modes
All Modes
SIEP_C710616_38F_5_0.book 406 ページ 2015年11月9日 月曜日 午後3時36分