B.3 Parameter Table
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 407
Parameter List
B
F5: Digital Output Card (DO-A3)
F6: Communication Option Card
For more details on a specific option card, refer to the instruction manual for the option card.
F4-05
(395H)
Terminal V1 Bias
Sets the amount of bias added to the voltage output via terminal V1.
Default: 0.0%
Min: -999.9%
Max: 999.9%
199
F4-06
(396H)
Terminal V2 Bias
Sets the amount of bias added to the voltage output via terminal V2.
Default: 0.0%
Min: -999.9%
Max: 999.9%
199
F4-07
(397H)
Terminal V1 Signal Level
Selection
0: 0 to 10 V
1: -10 to 10 V
Default: 1
Min: 0
Max: 1
200
F4-08
(398H)
Terminal V2 Signal Level
Selection
Default: 1
Min: 0
Max: 1
200
No.(Addr.) Name Description Setting Page
F5-01
(399H)
Terminal P1-C1 Output Selection
Sets the function for contact output terminals M1-M2, M3-M4, and photocoupler output
terminals P1 through P6.
Default: 0
Min: 0
Max: 161
200
F5-02
(39AH)
Terminal P2-C2 Output Selection
Default: 1
Min: 0
Max: 161
200
F5-03
(39BH)
Terminal P3-C3 Output Selection
Default: 2
Min: 0
Max: 161
200
F5-04
(39CH)
Terminal P4-C4 Output Selection
Default: 4
Min: 0
Max: 161
200
F5-05
(39DH)
Terminal P5-C5 Output Selection
Default: 6
Min: 0
Max: 161
200
F5-06
(39EH)
Terminal P6-C6 Output Selection
Default: 37
Min: 0
Max: 161
200
F5-07
(39FH)
Terminal M1-M2 Output Selection
Default: F
Min: 0
Max: 161
200
F5-08
(3A0H)
Terminal M3-M4 Output Selection
Default: F
Min: 0
Max: 161
200
F5-09
(3A1H)
DO-A3 Output Mode Selection 0: Output terminals are each assigned separate output functions.
1: Binary code output
2: Use output terminal functions selected by parameters F5-01 through F5-08.
Default: 0
Min: 0
Max: 2
200
No.(Addr.) Name Description Setting Page
F6-01
(3A2H)
Operation Selection after
Communications Error
0: Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only.
Default: 1
Min: 0
Max: 3
201
F6-02
(3A3H)
External Fault from
Communication Option Detection
Selection
0: Always detected
1: Detection during run only
Default: 0
Min: 0
Max: 1
201
F6-03
(3A4H)
External Fault from
Communication Option Operation
Selection
0: Ramp to stop. Decelerate to stop using the deceleration ramp in C1-02.
1: Coast to stop.
2: Fast Stop. Decelerate to stop using the deceleration ramp in C1-09.
3: Alarm only.
Default: 1
Min: 0
Max: 3
201
F6-04
(3A5H)
bUS Error Detection Time
Sets the delay time for error detection if a bus error occurs.
Default: 2.0 s
Min: 0.0 s
Max: 5.0 s
No.(Addr.) Name Description Setting Page
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly
All Modes
common_
TMonly