8.2 Drive Options and Peripheral Devices
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 353
Peripheral Devices &
Options
8
8.2 Drive Options and Peripheral Devices
The following table of peripheral devices lists the names of the various accessories and options available for Yaskawa
drives. Contact Yaskawa or your Yaskawa agent to order these peripheral devices.
Peripheral Device Selection: Refer to the Yaskawa catalog for selection and part numbers.
Peripheral Device Installation: Refer to the corresponding option manual for installation instructions.
Table 8.1 Available Peripheral Devices
Option Model Number Description
Power Options
DC Link Choke UZDA Series
Improves the power factor by suppressing harmonic distortion
from the power supply.
AC Reactor UZBA Series
Protects the drive when operating from a large power supply
and improves the power factor by suppressing harmonic
distortion. Highly recommended for power supplies that exceed
600 kVA.
Braking Resistor Unit LKEB Series
For use with systems requiring dynamic braking with up to
10% ED.
Braking Unit CDBR Series External braking transistor
Molded Case Circuit Breaker NF Series
Circuit breaker for short circuit or over load protection
Note: Yaskawa recommends installing an MCCB to the power
supply side to protect drive wiring and prevent other damage in
the event of component failure. Install an MCCB if permitted
by the power system.
Electric Leakage Circuit Breaker
(ELCB)
NV, EG, or SG Series
Provides protection against potentially harmful leakage current.
Note: Yaskawa recommends installing an ELCB to the power
supply side to protect drive wiring and prevent other damage in
the event of component failure. An MCCB can also be used if
permitted by the power system.
Magnetic Contactor (Input) SC Series
Ensures that power to drive is completely shut off when
necessary, preventing potential damage to the braking resistor
and other internal circuitry.
Install an MCCB when using a braking resistor to prevent the
braking resistor from overheating.
To protect internal components from sudden high levels of
input current, the MC should be wired so that it opens when a
fault output terminal is triggered.
Surge Protector
200 V class: DCR2-A
400 V class: RFN3AL-504KD
Suppresses surge voltage caused by magnetic contactor
switching.
Zero Phase Reactor F6045GB, F11080GB Reduces electromagnetic noise.
Fuse
200 V class: CR2LS or CR2L Series, FWX Series
400 V class: CR6L Series, FWH Series
600 V class: FWP Series
Protects the drive in case of short circuit.
Input Noise Filter LNFB, LNFD, FN Series
Reduces electromagnetic noise flowing back from the drive
into power supply.
Output Noise Filter LF-310 Series Reduces electromagnetic noise generated by the drive output.
Isolator DGP Isolates the drive analog I/Os for improved noise tolerance.
Reference Setting / Monitor Options
Frequency Meter / Ammeter DCF-6A
External meter for displaying the output speed or current using
an analog signal from the drive
Frequency Meter Potentiometer
(20 kΩ)
RH000850
External potentiometer for adjusting the frequency meter
scaling
Output Voltage Meter SDF-12NH
External meter for displaying the output voltage using an
analog signal from the drive
Frequency Setting Potentiometer
(2 kΩ)
RH000739
External potentiometer for setting the speed reference by an
analog input
Control Dial for Frequency Setting
Potentiometer
CM-3S Control dial for frequency setting potentiometer
Meter Plate NPJT41561-1 Plate with scale for frequency setting potentiometer