A.2 Three-Phase 400 V Class Drives
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 379
A.2 Three-Phase 400 V Class Drives
Table A.2 Power Ratings (Three-Phase 400 V Class)
Item Specification
CIMR-LU4 0005 0006 0007 0009 0015 0018 0024 0031 0039 0045 0060
Maximum Applicable Motor Capacity (HP)
<1>
2 3 5 7.5 10 15 20 25 25-30 25-30 40
Input
Input Current (A)
<2>
3.65.18.31216233138444358
Rated Voltage
Rated Frequency
Three-phase 380 to 480 Vac 50/60 Hz 510 to 680 Vdc
<3>
Allowable Voltage Fluctuation -15 to 10%
Allowable Frequency
Fluctuation
±5%
Input Power (kVA) 4.15.89.5141826354346.6 39.3 53.0
Output
Rated Output Capacity
(kVA)
<4>
3.5
<5>
4.1
<5>
6.3
<5>
9.8
<5>
12
<5>
17
<5>
22
<5>
27
<5>
30
<5>
34
<5>
48
<5>
Rated Output Current (A)
3.5
<5>
4.1
<5>
6.3
<5>
9.8
<5>
12
<5>
17
<5>
22
<5>
27
<5>
39
<5>
45
<5>
60
<5>
Overload Tolerance 150% of rated output current for 60 s
Carrier Frequency User adjustable between 2 and 15 kHz
Maximum Output Voltage (V) Three-phase 380 to 480 V (proportional to input voltage)
Maximum Output Speed (Hz) 200 Hz (user-adjustable)
Item
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater
than the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
conditions, and power supply impedance.
<3> DC is not available for UL standards.
<4> Rated motor capacity is calculated with a rated output voltage of 440 V.
<5> Carrier frequency can be set up to 8 kHz while keeping this current rating. Higher carrier frequency settings require derating.
<6> Carrier frequency can be set up to 5 kHz while keeping this current rating. Higher carrier frequency settings require derating.
<7> Carrier frequency can be set up to 2 kHz while keeping this current derating. Higher carrier frequency settings require derating.
Specification
CIMR-LU4 0075 0091 0112 0150 0180 0216 0260 0304 0370 0450 0605
Maximum Applicable Motor Capacity (HP)
<1>
50-60 50-60 75 100 125-150 150 200 250 300 350
400-450-
500
Input
Input Current (A)
<2>
71 86 105 142 170 207 248 300 346 410 584
Rated Voltage
Rated Frequency
Three-phase 380 to 480 Vac 50/60 Hz 510 to 680 Vdc
<3>
Allowable Voltage Fluctuation -15 to 10%
Allowable Frequency
Fluctuation
±5%
Input Power (kVA) 64.9 78.6 96.0 129.9 155 189 227 274 316 375 534
Output
Rated Output Capacity
(kVA)
<4>
57
<5>
69
<5>
85
<6>
114
<6>
137
<6>
165
<6>
198
<6>
232
<6>
282
<6>
343
<7>
461
<7>
Rated Output Current (A)
75
<5>
91
<5>
112
<6>
150
<6>
180
<6>
216
<6>
260
<6>
304
<6>
370
<6>
450
<7>
605
<7>
Overload Tolerance 150% of rated output current for 60 s
Carrier Frequency
User adjustable
between 2 and 15 kHz
User adjustable between 2 and 10 kHz
User-adjustable
between
2 and 5 kHz
Maximum Output Voltage (V) Three-phase 380 to 480 V (proportional to input voltage)
Maximum Output Speed (Hz) 200 Hz (user-adjustable) 400 Hz (user-adjustable)