D.2 European Standards
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 475
20145 50 136 250 225 350 FWH-400A (400)
20180 60 164 300 250 450 FWH-400A (400)
20215 75 200 400 350 600 FWH-600A (600)
20283 100 271 500 450 800 FWH-700A (700)
20346 125 324 600 500 900
<5>
FWH-800A (800)
20415 150 394 700 600 1100
<5>
FWH-1000A (1000)
Three-Phase 400 V Class
40005 3 4.4 15 7 12 FWH-70B (70)
40006 3 6 15 10 17.5 FWH-70B (70)
40007 5 8.2 15 12 20 FWH-90B (90)
40009 5 10.4 20 17.5 30 FWH-90B (90)
40015 7.5 15 30 25 40 FWH-80B (80)
40018 10 20 40 35 60 FWH-100B (100)
40024 15 29 50 50 80 FWH-125B (125)
40031 20 39 75 60 110 FWH-200B (200)
40039 25 47 75 75 125 FWH-250A (250)
40045 30 43 75 75 125 FWH-250A (250)
40060 40 58 100 100 150 FWH-250A (250)
40075 60 71 125 110 200 FWH-250A (250)
40091 60 86 150 150 250 FWH-250A (250)
40112 75 105 175 175 300 FWH-350A (350)
40150 100 142 225 225 400 FWH-400A (400)
40180 125 170 250 250 500 FWH-500A (500)
40216 150 207 350 350 600 FWH-600A (600)
40260 200 248 400 400 700 FWH-700A (700)
40304 250 346 600 600 1000
<5>
FWH-800A (800)
40370 300 410 800 700 1200
<5>
FWH-800A (800)
40450 350 465 900 800 1350
<5>
FWH-1000A (1000)
40605 400-450-500 657 1200 1100
<5>
1800
<5>
FWH-1200A (1200)
Three-Phase 600 V Class
50003
<6>
2 3.6 15 6.25 10 FWP-50B (50)
50004
<6>
3 5.1 15 8 15 FWP-60B (60)
50006
<6>
5 8.3 15 12 20 FWP-60B (60)
50010
<6>
7.5 12 20 20 35 FWP-70B (70)
50013
<6>
10 16 30 25 45 FWP-100B (100)
50017
<6>
15 23 40 40 60 FWP-100B (100)
50022
<6>
20 31 60 50 90 FWP-125A (125)
50027
<6>
25 38 75 60 100 FWP-125A (125)
50032
<6>
25-30 33 60 50 90 FWP-175A (175)
50041
<6>
40 44 75 75 125 FWP-175A (175)
50052
<6>
50-60 54 100 90 150 FWP-250A (250)
50062
<6>
50-60 66 125 110 175 FWP-250A (250)
50077
<6>
75 80 150 125 225 FWP-250A (250)
50099
<6>
100 108 175 175 300 FWP-350A (350)
50130
<6>
125 129 250 225 350 FWP-350A (350)
50172
<6>
150 158 300 250 400 FWP-600A (600)
50200
<6>
200 228 400 350 600 FWP-600A (600)
<1> Maximum MCCB Rating is 15 A, or 200% of drive input current rating, whichever is larger. MCCB voltage rating must be 600 VAC or greater.
<2> Maximum Time Delay fuse is 175% of drive input current rating. This covers any Class CC, J or T class fuse.
<3> Maximum Non-time Delay fuse is 300% of drive input current rating. This covers any CC, J or T class fuse.
<4> When using semiconductor fuses, Bussmann FWH and FWP are required for UL compliance. Select FWH for 240 V and 480 V models and
FWP fuses for 600 V models.
<5> Class L fuse is also approved for this rating.
<6> 600 V class drives are not compliant with European Standards.
Drive Model
CIMR-LU
L1000
Nominal Output
Power HP
AC Drive Input
Amps
MCCB Rating
Amps
<1>
Time Delay Fuse
Rating Amps
<2>
Non-time Delay
Fuse Rating Amps
<3>
Bussmann
Semi-conductor Fuse Rating
(Fuse Ampere)
<4>