5.11 S: Elevator Parameters
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 259
Parameter Details
5
S1-05: DC Injection / Position Lock Time at Stop
Determines how long the drive should perform DC Injection at stop. In CLV and CLV/PM, S1-05 determines how long
Position Lock should be performed. A setting of 0.00 disables S1-05.
S1-06: Brake Release Delay Time
Determines the time that must pass after an Up/Down command is entered before the output terminal set for “Brake
control” (H2- = 50) is triggered.
Adjusting this delay time can help when there is not enough time to develop the appropriate amount of motor flux. Be
sure to also increase the time S1-04 when setting S1-06 to relatively long delay time.
S1-07: Brake Close Delay Time
Determines the time that must pass after zero speed is reached before the output terminal set for "Brake control"
(H2- = 50) is released.
S1-10: Run Command Delay Time
Sets the time the drive waits after receiving an Up/Down command before starting operation. The time set should give the
motor contactor enough time to close.
S1-11: Output Contactor Open Delay Time
Determines the time that must pass for an output terminal set for “Output contactor control” (H2- = 51) to be released
after the drive has stopped and drive output has been shut off.
S1-12: Motor Contactor Control During Auto-Tuning Selection
Note: Available in drive software PRG: 7016 or later.
Determines the state of the output contactor control command (H2- = 51) during Auto-Tuning. The contactor closes
as soon as the Enter key is pressed in the Auto-Tuning start menu.
No. Parameter Name Setting Range Default
S1-05 DC Injection / Position Lock Time at Stop 0.00 to 10.00 s 0.60 s
No. Parameter Name Setting Range Default
S1-06 Brake Release Delay Time 0.00 to 10.00 s 0.20 s
No. Parameter Name Setting Range Default
S1-07 Brake Close Delay Time 0.00 to [S1-05] 0.10 s
No. Parameter Name Setting Range Default
S1-10 Run Command Delay Time 0.00 to 1.00 s 0.10 s
No. Parameter Name Setting Range Default
S1-11 Output Contactor Open Delay Time 0.00 to 1.00 s 0.10 s
No.
<1> Setting 2 is available in drive software versions PRG: 7017 or later.
<2> The setting is 0 or 1 for software version PRG: 7016.
Parameter Name Setting Range Default
S1-12 Motor Contactor Control during Auto-Tuning 0 to 2
<1> <2>
0