5.7 H: Terminal Functions
212 YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Setting E: Fault
The output closes when the drive faults (excluding CPF00 and CPF01 faults).
Setting F: Not used (Through mode)
Select this setting when using the terminal in a pass-through mode. When set to F, an output does not trigger any function
in the drive. Setting F, however, still allows the output status to be read by a PLC via a communication option or
MEMOBUS/Modbus communications.
Setting 10: Minor fault
Output closes when a minor fault condition is present.
Setting 11: Fault reset command active
Output closes whenever there is an attempt to reset a fault situation from the control circuit terminals, via serial
communications, or using a communications option card.
Setting 12: Timer output
This setting configures a digital output terminal as output for the timer function. Refer to b4: Delay Timers on page 169
for details.
Setting 13: Speed agree 2 (f
ref
/f
out
agree 2)
Closes whenever the actual output speed or motor speed (CLV, CLV/PM) is within the speed agree width (L4-04) of the
current speed reference, regardless of the direction.
Note: Detection works in both forward and reverse.
Figure 5. 23
Figure 5.23 Speed Agree 2 Time Chart
Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 229 for more details.
Setting 14: User-set speed agree 2 (f
ref
/f
set
agree 2)
Closes whenever the actual output speed or motor speed (CLV, CLV/PM) and the speed reference are within the speed
agree width (L4-04) of the programmed speed agree level (L4-03). As the detection level L4-03 is a signed value,
detection works in the specified direction only.
Status Description
Open Output speed or motor speed does not match the speed reference while the drive is running.
Closed Output speed or motor speed is within the range of speed reference ±L4-04.
Status Description
Open Output speed or motor speed and speed reference are both outside the range of L4-03 ±L4-04.
Closed Output speed or motor speed and the speed reference are both with in the range of L4-03 ±L4-04.
L4-04
L4-04
Speed
reference
Speed Agree 2
ON
OFF
Output speed
or motor speed
common_
TMonly
SIEP_C710616_38F_5_0.book 212 ージ 015年11月9日 月曜日 午後3時36分