5.9 n: Special Adjustments
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 247
■ n8-02: Pole Attraction Current
Sets the pull-in current used to detect rotor position. This setting rarely needs to be changed.
■
n8-35: Initial Rotor Position Detection Selection
Selects how the rotor position is detected at start.
Setting 1: High Frequency Injection
High frequency is injected in order to detect the rotor position. Some noise may be generated from the motor at start.
Setting 2: Pulse injection
A pulse signal is injected into the motor in order to detect the rotor position.
■
n8-36: High Frequency Injection Level
Sets the frequency level used for High Frequency Injection.
■
n8-37: High Frequency Injection Amplitude
Sets the amplitude for High Frequency Injection as a percentage of the voltage (200 V or 400 V or 575 V).
■
n8-81: High Frequency Injection during Rescue Operation
Sets the frequency used for High Frequency Injection during Rescue Operation.
■
n8-82: High Frequency Injection Amplitude during Rescue Operation
Sets the amplitude for High Frequency Injection during Rescue Operation as a percentage of the voltage (200 V or 400 V
or 575 V).
■
n8-84: Polarity Detection Current
Sets the current level (E5-03) as a percentage for detecting polarity during Initial Polarity Estimation.
■
n8-86: Magnet Pole Search Error Detection Selection
Enables fault detection for Initial Polarity Estimation (dv8).
No. Parameter Name Setting Range Default
n8-02 Pole Attraction Current 0 to 150% 80%
No. Parameter Name Setting Range Default
n8-35 Initial Rotor Position Detection Selection 1 or 2 1
No. Parameter Name Setting Range Default
n8-36 High Frequency Injection 25 to 1000 Hz 500 Hz
No. Parameter Name Setting Range Default
n8-37 High Frequency Injection Amplitude 0.0 to 99.9% 20.0%
No. Parameter Name Setting Range Default
n8-81 High Frequency Injection during Rescue Operation 25 to 1000 Hz 90 Hz
No. Parameter Name Setting Range Default
n8-82 High Frequency Injection Amplitude during Rescue Operation 0.1 to 99.9% 15.0%
No. Parameter Name Setting Range Default
n8-84 Polarity Detection Current 0 to 150% 100%
No. Parameter Name Setting Range Default
n8-86 Magnet Pole Search Error Detection Selection 0 or 1 0