EasyManua.ls Logo

YASKAWA L1000A - Page 71

YASKAWA L1000A
522 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.7 Main Circuit Wiring
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual 71
Electrical Installation
3
Note: When connecting peripheral devices and options to the terminals –, +1, +3, B1, and B2, refer to the instruction manuals for each
device. For more information, contact Yaskawa or your nearest sales representative.
Three-Phase 400 V Class
Table 3.3 Wire Gauge and Torque Specifications (Three-Phase 400 V Class)
20115
R/L1, S/L2, T/L3 2/0 10 to 3/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 2/0 10 to 3/0
–, +1 1/0 to 3/0
B1, B2 4 to 2/0
44M8
9 to 11
(79.7 to 97.4)
20145
R/L1, S/L2, T/L3 4/0 1/0 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 4/0 1/0 to 4/0
–, +1 1 to 4/0
+3 1/0 to 4/0
44 to 2
9 to 11
(79.7 to 97.4)
20180
R/L1, S/L2, T/L3 1/0 × 2P 1/0 to 4/0
M10
18 to 23
(159 to 204)
U/T1, V/T2, W/T3 1/0 × 2P 1/0 to 4/0
–, +1 1 to 4/0
+3 1/0 to 4/0
44 to 1/0
9 to 11
(79.7 to 97.4)
20215
R/L1, S/L2, T/L3 2/0 × 2P 3/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 2/0 × 2P 3/0 to 300
–, +1 3/0 to 300
+3 2 to 300 M10
18 to 23
(159 to 204)
3 3 to 300 M12
32 to 40
(283 to 354)
20283
R/L1, S/L2, T/L3 3/0 × 2P 3/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 3/0 × 2P 3/0 to 300
–, +1 3/0 to 300
+3 3/0 to 300 M10
18 to 23
(159 to 204)
2 2 to 300 M12
32 to 40
(283 to 354)
20346
R/L1, S/L2, T/L3 250 × 2P 4/0 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 4/0 × 2P 4/0 to 600
–, +1 250 to 600
+3 3/0 to 600 M10
18 to 23
(159 to 204)
1 1 to 350 M12
32 to 40
(283 to 354)
20415
R/L1, S/L2, T/L3 350 × 2P 250 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 300 × 2P 300 to 600
–, +1 300 to 600
+3 3/0 to 600 M10
18 to 23
(159 to 204)
1 1 to 350 M12
32 to 40
(283 to 354)
<1> When using the wire of this gauge in accordance with IEC/EN 61800-5-1, install an ELCB.
<2> When using the wire of this gauge in accordance with IEC/EN 61800-5-1, install an ELCB, or use copper wire of 10 mm
2
(AWG 8).
Model
CIMR-LU
Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
Nm (lb.in.)
40005
40006
40007
R/L1, S/L2, T/L3 14 14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3 14 14 to 10
–, +1, +2 14 to 10
B1, B2 14 to 10
10
<1>
14 to 10
Model
CIMR-LU
Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
Nm (lb.in.)
SIEP_C710616_38F_5_0.book 71 ペー 2015年11月9日 月曜日 午後3時36