Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
8
Supervision 1 active (32.1 Supervision status, bit 0).
Supervision 1
9
Supervision 2 active (32.1 Supervision status, bit 1).
Supervision 2
10
Supervision 3 active (32.1 Supervision status, bit 2).
Supervision 3
11Motor temperature estimation is performed always with
drive start command.
Drive start command
12Motor temperature estimation is performed once after drive
power-up (control board boot).
Drive power-up
4.0 s / real32Defines the motor temperature estimation time.
Motor temperature estimation is activated with parameter
21.37 Motor temperature estimation.
Motor temperature
estimation time
21.38
10 = 1 s / 10 = 1 sMotor temperature estimation time in seconds.0.5 ... 20.0 s