EasyManua.ls Logo

ABB ACS880 - Page 450

ABB ACS880
646 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
0 = Status of follower 19 is monitored continuously.
1 = Status of follower 19 is monitored only when it is in
stopped state.
Follower 19b2
0 = Status of follower 20 is monitored continuously.
1 = Status of follower 20 is monitored only when it is in
stopped state.
Follower 20b3
0 = Status of follower 21 is monitored continuously.
1 = Status of follower 21 is monitored only when it is in
stopped state.
Follower 21b4
0 = Status of follower 22 is monitored continuously.
1 = Status of follower 22 is monitored only when it is in
stopped state.
Follower 22b5
0 = Status of follower 23 is monitored continuously.
1 = Status of follower 23 is monitored only when it is in
stopped state.
Follower 23b6
0 = Status of follower 24 is monitored continuously.
1 = Status of follower 24 is monitored only when it is in
stopped state.
Follower 24b7
0 = Status of follower 25 is monitored continuously.
1 = Status of follower 25 is monitored only when it is in
stopped state.
Follower 25b8
0 = Status of follower 26 is monitored continuously.
1 = Status of follower 26 is monitored only when it is in
stopped state.
Follower 26b9
0 = Status of follower 27 is monitored continuously.
1 = Status of follower 27 is monitored only when it is in
stopped state.
Follower 27b10
0 = Status of follower 28 is monitored continuously.
1 = Status of follower 28 is monitored only when it is in
stopped state.
Follower 28b11
0 = Status of follower 29 is monitored continuously.
1 = Status of follower 29 is monitored only when it is in
stopped state.
Follower 29b12
0 = Status of follower 30 is monitored continuously.
1 = Status of follower 30 is monitored only when it is in
stopped state.
Follower 30b13
0 = Status of follower 31 is monitored continuously.
1 = Status of follower 31 is monitored only when it is in
stopped state.
Follower 31b14
0 = Status of follower 32 is monitored continuously.
1 = Status of follower 32 is monitored only when it is in
stopped state.
Follower 32b15
1 = 10000h…FFFFh
60.0 s / uint16Defines a wake-up delay during which no master/follower
communication faults or warnings are generated. This is
to allow all drives on the master/follower link to power up.
The master cannot be started until the delay elapses or all
monitored followers are found to be ready.
M/F wake up delay60.31
450 Parameters

Table of Contents

Other manuals for ABB ACS880

Related product manuals