Def / Type
FbEq 16b / 32b
DescriptionName / Range /
Selection
No.
10 = 1 s / 10 = 1 sMaster/follower wake-up delay.0.0 ... 180.0 s
- / uint16Activates master/follower communication monitoring
separately for each control location (see section Local
control vs. external control (page 23)).
The parameter is primarily intended for monitoring the
communication with master or follower when it is connected
to the application program and not selected as a control
source by drive parameters.
M/F comm
supervision force
60.32
1 = Communication monitoring active when Ext 1 is being
used.
Ext 1b0
1 = Communication monitoring active when Ext 2 is being
used.
Ext 2b1
1 = Communication monitoring active when local control
is being used.
Localb2
Reservedb3…15
1 = 10000h…FFFFh
Not in use / uint16Selects the channel used for connecting an optional FEA-xx
extension adapter.
Extension adapter
com port
60.41
0None (communication disabled).Not in use
1Channel A on FDCO module in slot 1.Slot 1A
2Channel A on FDCO module in slot 2.Slot 2A
3Channel A on FDCO module in slot 3.Slot 3A
4Channel B on FDCO module in slot 1.Slot 1B
5Channel B on FDCO module in slot 2.Slot 2B
6Channel B on FDCO module in slot 3.Slot 3B
13Channel CH 3 on RDCO module (with BCU control unit
only).
RDCO CH 3
ABB engineered drive
/ uint16
In ModuleBus communication, defines whether the drive
is of the “engineered” or “standard” type.
Note: This parameter cannot be changed while the drive
is running.
DDCS controller drive
type
60.50
0The drive is an “engineered drive” (data sets 10…25 are
used).
ABB engineered drive
1The drive is a “standard drive” (data sets 1…4 are used).ABB standard drive
Not in use / uint16Selects the DDCS channel used for connecting an external
controller (such as an AC 800M).
DDCS controller
comm port
60.51
0None (communication disabled).Not in use
1Channel A on FDCO module in slot 1.Slot 1A
2Channel A on FDCO module in slot 2.Slot 2A
3Channel A on FDCO module in slot 3.Slot 3A
4Channel B on FDCO module in slot 1.Slot 1B
5Channel B on FDCO module in slot 2.Slot 2B
Parameters 451