What to doCause
Event name /
Aux. code
Code
(hex)
“Clean all” command, and reload the
application.
Update the system library or reinstall
Automation Builder.
The application contains an unknown
target (system) library function.
800A
See the drive-specific log generated
by Automation Builder.
Record the auxiliary codes of all active
licensing faults and contact your product
vendor for further instructions.
Running the control program is prevented
either because a restrictive license
exists, or because a required license is
missing.
Licensing fault64A5
Check the auxiliary code (format XXXX
YYYY). “XXXX” specifies the number of
Error running the adaptive program.Adaptive
program
64A6
the function block (0000 = generic error).
“YYYY” indicates the problem (see
actions for each code below).
Restore the template program or
download the program to the drive.
Program corrupted or block
non-existent.
000A
Check the inputs of the block.Required block input missing.000C
Restore the template program or
download the program to the drive.
Program corrupted or block
non-existent.
000E
Remove blocks until the error stops.Program too large.0011
Correct the program and download it
to the drive.
Program is empty.0012
Edit the program to correct the
parameter reference, or to use an
existing block.
A nonexisting parameter or block is
used in the program.
001C
Edit the program to correct the
parameter reference.
Parameter type invalid for selected pin.001D
Check the parameter reference in the
program.
Output to parameter failed because
the parameter was write-protected.
001E
Check for other sources affecting the
target parameter.
Adapt the program to current block
library and firmware version.
Program file incompatible with current
firmware version.
0023, 0024
Edit the program to reduce the number
of blocks.
Too many blocks.002A
Switch off the power to the control unit
and reinstall the memory unit.
The memory unit was detached when
the control unit was powered.
Memory unit
detached
64B0
In case the memory unit was not actually
removed when the fault occurred, check
that the memory unit is properly inserted
into its connector and its mounting screw
is tight. Reboot the control unit (using
parameter 96.8 Control board boot) or
by cycling power. If the problem persists,
contact your local ABB representative.
Reboot the control unit (using parameter
96.8 Control board boot) or by cycling
Internal fault.Internal SSW
fault
64B1
power. If the problem persists, contact
your local ABB representative.
Fault tracing 551