EasyManuals Logo

ABB CL Series User Manual

ABB CL Series
428 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #228 background imageLoading...
Page #228 background image
Function blocks
225
1SVC 440 795 M1100
Parameter display and parameter set for the LS
function block:
Inputs
The function block inputs
>I1, >X1, >X2, >Y1 and >Y2
can have the following operands:
•Constants
Markers MD, MW, MB
Analog inputs IA01 to IA04
IA01: Terminal I7
IA02: Terminal I8
IA03: Terminal I11
IA04: Terminal I12
Analog output QA01
Actual value …QV> of another function block
Output
The function block output QV> can have the following
operands:
Markers MD, MW, MB
Analog output QA01
LS27 +
>I1
>X1
>Y1
>X2
>Y2
QV>
LS27 LS value scaling function block number 27
+ Appears in the parameter display
>I1 Input value, actual value source range
>X1 Lower value of source range
>Y1 Lower value of target range
>X2 Upper value of source range
>Y2 Upper value of target range
QV> Output value, scaled

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB CL Series and is the answer not in the manual?

ABB CL Series Specifications

General IconGeneral
ManufacturerABB
Rated Control Supply Voltage (Us)24 V DC
MountingDIN Rail
CategoryRelays
Contact ConfigurationSPDT
Coil Voltage24 V DC
Operating Temperature-40°C to +70°C
Electrical Life100 Thousand Cycles
OutputRelay

Related product manuals