Output Type Description
Walk Test* This output turns on momentarily when a walk test is operational and a zone becomes active.
This output can be used, for example, to activate functional tests of connected detectors (if
available).
Auto Set This output turns on if the Auto Set feature has been activated on the system.
User Duress This output turns on if a user duress state has been activated (PIN code + 1 has been entered
on the keypad).
PIR Masked This output turns on if there are any masked PIR zones on the system. It generates a fault
output on the keypad led.
This output is latched so it will remain active until restored by a level 2 user.
PIR Masking is logged by default. The number of log entries do not exceed 8 between arming
periods.
Zone Omitted This output turns on if there are any inhibited, isolated, or walk test zones on the system.
Fail to
Communicate
This output turns on if there is a failure to communicate to the central station.
Man Down Test This output turns on a ‘Man Down’ wireless device which is activated during a ‘Man Down’
test.
Unset This output is activated if the system is in Unset mode.
Alarm Abort This output activates if an alarm abort event occurs, that is, when a valid user code is entered
via the keypad after a confirmed or unconfirmed alarm. It is used, for example, with external
dialers (SIA, CID, FF).
Seismic Test This output is used to activate a manual or automatic test on a seismic zone. Seismic sensors
have a small vibrator that will be attached to the same wall as the sensor and is wired to an
output on the panel or one of its expanders. During the test, the panel waits up to 30 seconds
for the seismic zone to open. If it does not open, the test fails. If it opens within 30 seconds the
panel then waits for the zone to close within 10 seconds. If that doesn’t happen, the test fails.
The panel then waits a further 2 seconds before reporting the test result. The result of the
test, either manual or automatic, is stored in the system event log.
Local Alarm This output activates on a local intrusion alarm.
RF Output
This output activates when a Fob or WPA1 button is pressed.
Modem 1 Line
Fault
This output activates when there is a line fault on the primary modem.
Modem 1
Failure
This output activates when the primary modem fails.
Modem 2 Line
Fault
This output activates when there is a line fault on the secondary modem.
Modem 2
Failure
This output activates when the secondary modem fails.
Battery Low This output activates when the battery is low.