Zone Type
Processing
Category
Description
KEYARM Intruder This zone type is normally used in conjunction with a key lock
mechanism.
A Keyarm can be configured to perform the following Setting Options:
l
Fullset
l
Partset A
l
Partset B
A Keyarm zone will SET the System/Area/Common Areas according to
the selected Setting Option when it is OPENED and will UNSET the
System/Area/Common Areas according to the selected Setting
Option when it is CLOSED.
l
If the zone with the keyarm zone type is assigned in an non area
system then the keyarm operation will SET/UNSET the system.
l
If the zone with the keyarm zone type is assigned to an area then
the keyarm operation will SET/UNSET the area.
l
If the zone with the keyarm zone type is assigned to a common
area then the keyarm operation will SET/UNSET all the areas in
the common area.
l
If the ‘Open only’ attribute is set then the armed status of the
System/Area/Common Areas will toggle on each opening of the
key lock (that is, Open once to SET the system, Close and Open
again to UNSET).
l
If the ‘Fullset Enable’ attribute is set then zone activation will only
Fullset the system.
l
If the ‘Unset Enable’ attribute is set then zone activation will only
unset the system.
Keyarming will force set the system/area and auto-inhibit any open
zones or fault conditions.
Note: Your system will not comply with EN standards if you
enable this zone type to set the system without first entering a
valid PIN on an external device.
SHUNT Intruder This zone type is only available in Commercial Mode of operation.
Though the Shunt Alarm Zone type can be set in Domestic Mode of
operation, it has no effect.
This zone type when opened inhibits all zones that have the shunt
attribute set. This operation applies for both SET and UNSET modes.
As soon as the shunt zone is closed, the zones with the shunt attribute
set will become un-inhibited again.
X-SHUNT Intruder This zone type is only available in Commercial Mode of operation.
A zone programmed with the x-shunt zone type inhibits the next
consecutive zone on the system whenever it is opened. This operation
applies for both SET and UNSET modes. As soon as the x-shunt zone
type is closed the next zone becomes de-inhibited again.
SPC42/52/53/63 Installation & Configuration Manual Appendix
© Vanderbilt 2023 280 I-200572
08.12.2023