Timer Description Default
Engineer auto log out
ENG AUTO LOG OUT
Duration of inactivity after which the engineer will be
automatically logged out. (0–300 minutes)
0 min.
Keypad
Keypad Timeout
KEYPAD TIMEOUT
The number of seconds that an RKD will wait for key entry
before it leaves the current menu. (10–300 seconds)
30 sec.
Keypad Language
KEYPAD LANGUAGE
The duration a keypad will wait in idle before switching
language to default. (0–9999 seconds; 0=never)
10 sec.
CODELOCKOUT 10 sec
CODE LOCKOUT 2 10 sec
Lockout time 90 sec
Fire
Fire Pre-alarm
FIRE PRE-ALARM
Number of seconds to wait before reporting fire alarm for zones
with ‘Fire pre-alarm’ attribute set. See Editing a zone on
page185. (1–999 seconds)
30sec.
Fire recognition
FIRE RECOGNITION
Extra time to wait before reporting file alarm for zones with ‘Fire
pre-alarm’ and ‘Fire Recognition’ attributes set. See Editing a
zone on page185. (1–999 seconds)
120sec.
PIN
PIN Valid
PIN VALID
Period for which pin is valid. (1–330 days) 30 days
PIN Changes Limit
PIN CHANGES LIMIT
Number of changes within a valid period. (1–50) 5
PIN Warning
PIN WARN
Time before PIN expiry after which a warning will be displayed.
(1–14 days)
5 days
General Settings
RF Output Time
RF OUTPUT
The time that the RF output will remain active on the system.
(0–999 seconds)
0 sec.
Time Sync Limit
TIME SYNC LIMIT
Time limit within which time synchronization will not take place.
Time synchronization only takes place if system time and
update time are outside this limit. (0–300 seconds)
0 sec.
Link Timeout
LINK TIMEOUT
Timeout for Ethernet link fault. (0–250 seconds; 0=Disabled) 0 sec.
Camera Offline
CAMERA OFFLINE
Time for camera to go offline. (10–9999 seconds) 10 sec.
SPC42/52/53/63 – Installation & Configuration Manual Engineer programming via the keypad
© Vanderbilt 2023 74 I-200572