DESCRIPTION Name of the door controller
DOORS Configuration of Door I/O 1 and Door I/O 2.
READERS Configuration of Reader Profiles
To edit a DOOR I/O:
1. Scroll to DOORS.
2. Press SELECT.
3. Scroll to the DOOR I/O to be edited and press SELECT.
Parameters and details, if applicable, are displayed for editing as shown in the table below.
ZONES No access functionality is realized. The inputs and outputs can be
used normally.
DOOR 1 – DOOR
64
The selected door number is assigned to the DOOR I/O.
If the option “ZONES” is selected for a DOOR I/O the two inputs of this door I/O must be configured:
To edit the two zones of a DOOR I/O:
1. Scroll to the DOOR I/O to be edited and press SELECT
The option “Zones” is selected.
2. Press SELECT.
3. Select which Zone should be edited (DPS or DRS zone).
4. Press SELECT.
Parameters and details, if applicable, are displayed for editing as shown in the table below.
UNASSIGNED This zone is not assigned and can not be used.
ZONE 1 – ZONE
512
The zone which is edited is assigned to this zone number. If the zone
is assigned to a specific zone number, it can be configured like a
normal zone.
The zones can be assigned to each free zone number. But the assignment is not fixed. If the
zone was assigned to zone number 9 and an input expander with the address 1 is connected to
the X-Bus (which is using the zone numbers 9–16) the assigned zone from the two door
controller will be moved to the next free zone number. The configuration will be adapted
accordingly.
To edit a READER PROFILE:
1. Scroll to READERS.
2. Press SELECT.
3. Scroll to the READER to be edited and press SELECT.
Select any of the following profiles for the reader:
1 For readers with a green and a red LED.
2 For VANDERBILT readers with a yellow LED (AR618X).
SPC42/52/53/63 – Installation & Configuration Manual Engineer programming via the keypad
© Vanderbilt 2023 86 I-200572
08.12.2023