EasyManua.ls Logo

Alcatel-Lucent 7750 SR - Figure 69: MC-EP with B-VPLS

Alcatel-Lucent 7750 SR
1948 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Virtual Private LAN Services
7750 SR OS Services Guide Page 467
Figure 69: MC-EP with B-VPLS
Multiple I-VPLS instances may be used to represent in the gateway PEs the customer VPLS
instances using PBB-VPLS M:1 model described in the PBB section. A backbone VPLS (B-
VPLS) is used in this example to administer the resiliency for all customer VPLS instances at the
domain borders. Just one MC-EP is required to be configured in the B-VPLS to address 100s or
even 1000s of customers VPLS instances. If load balancing is required, multiple B-VPLS
instances may be used to ensure even distribution of the customers across all the pseudowires
interconnecting the two domains. In this example, four B-VPLS will be able to loadshare the
customers across all four possible pseudowire paths.
The use of MC-EP with B-VPLS is strictly limited to cases where VPLS mesh exists on both sides
of a B-VPLS. For example, active/standby pseudowires resiliency in the I-VPLS context where
PE3, PE3’ are PErs cannot be used because there is no way to synchronize the active/standby
selection between the two domains.
For a similar reason, MC-LAG resiliency in the I-VPLS context on the gateway PEs participating
in the MC-EP (PE3, PE3) should not be used.
Note that for the PBB topology described in Figure 69, block-on-mesh-failure in the I-VPLS
domain will not have any effect on the B-VPLS MC-EP side. That is because mesh failure in one
I-VPLS should not affect other I-VPLS sharing the same B-VPLS.

Table of Contents

Other manuals for Alcatel-Lucent 7750 SR

Related product manuals