1756-6.5.3 - December 1999
6-18 Logix5550 Controller to PLC-5C: Scheduled Communications
To verify that the message is being received by the PLC-5C processor, you
must examine the input file configured in RSNetWorx for ControlNet (i.e.,
N9).
14.Double-click on file N9 in the Data Files folder.
You should see the value in N9:0 continuously changing to reflect the
data from the Logix5550 controller.
This completes the Logix5550 to PLC-5C scheduled communication
example.
Examine this file.
This value should be changing.