Chapter 5 Parameter Introductions
134
P7.12 PID preset frequency
Range:
3004GB/35R5PB and below:
0.00~650.0Hz0.00Hz
35R5GB/37R5PB and above:
0.00~400.0Hz0.00Hz
P7.13 Hold time of PID Preset frequency
Range: 0.0~3600s 0.0s
Note:
This function can make the PID regulation enter stable state quickly.
When the PID operation is start, the frequency will ramp up to the PID preset
frequency (P7.12) within the Acc time, and then the inverter will start PID
operation after operating at the PID preset frequency for a certain time (defined
by P7.13).
Preset
Frequency
Operation Freq.(Hz)
Time
Hold time of PID
Preset frequency
Fig. 5-7-2 PID preset frequency operation
Tips:
You can disable the function by setting the PID preset frequency (P7.12) to 0.
P7.14 Analog closed loop measuring range
Range: Max[P7.02,1.0]~999.9100.0
Note:
This parameter is treated as a benchmark of analog PID feed and feedback. In
addition, it must match the actual measuring range.
P7.15 Enable dormancy
Range: 0,10
0: Disable 1: Enable
Tips:
There is no standby function when the speed PID feed is used.
P7.16 Dormancy delay time
Range: 0~999s120s
P7.17 Dormancy threshold
Range: 0~Frequency upper limit20.00Hz
P7.18 Awakening threshold
Range: 0.0~999.93.0
Note: