Pd.16
Fig. 5-13-6 Acceleration speed over current
Pd.17 Automatic running selection after
power on
Setting range: 0,1【1】
0: No action after power on 1: Run automatically after power on
Notes:
No action after power on: Not allow to run automatically when power on.
Run automatically after power on: Originally general functions are reserved.
Pd.18 Running selection after power off
Setting range:0,1【0】
0:Machine shut down after power off
(through the shutdown way)
1:Machine does not shut down after
power off (short time)
Notes:
Machine shut down after power off: shut down according to the set way
Machine doesn’t shut down after power off: After power off, output can be held
in short time and can continue to run after power recovers. This function only
suits light load equipment, such as wind machines and water pumps etc. It needs
to combine other parameter and the detailed setting is given below:
Power<=22KW
Power>22KW
P0.21 Acceleration time 1 20s
60s
P2.28 Acceleration time 3 20s
60s
P2.29 Deceleration time 3 6s
20s
P1.15 Instantaneous stop
processing
2:Once instantaneous
stop, display Uu
2: Once instantaneous
stop, displays Uu