Chapter 4 Parameter Index
78
Function
code
Function Name Range of settings Default Change
MODBUS
Address
PE.04
DC bus voltage at
last fault
0~1000V 0V * 0F04
PE.05
Running status at
last fault
0: StP : Stop
1: Acc: Acceleration
2: Dec: Deceleration
3: con: constant
0 * 0F05
PE.06
Fault history 1
(Last One)
The same as PE.00 NULL * 0F06
PE.07 Fault history 2 The same as PE.00 NULL * 0F07
PE.08 Fault history 3 The same as PE.00 NULL * 0F08
PE.09
Total operating
time
0~65530h 0h * 0F09
PE.10
Total power on
time
0~65530h 0h * 0F0A
PE.11
Total
electric-consumpti
on (MWh)
0~9999MWh 0MWh * 0F0B
PE.12
Total
electric-consumpti
on (KWh)
0~999KWh 0KWh * 0F0C
PF: Protection of Parameters
Function
code
Function Name Range of settings Default Change
MODBUS
Address
PF.00 User password
0: No password
Others: Password protection
0 1000
PF.01
Parameter write-in
protection
0: All parameters are allowed to
modify
1: Only reference frequency (P0.00)
and PF.01 can be modified;
2: Only PF.01 can be modified.
0 1001
PF.02
Parameter
initialization
0: No operation
1: Clear fault history
2: Restore default
(except recorded data \ user password)
0 × 1002
PF.03
Reserve
(3004GB/35R5PB
or below)
Reserved 0 -
1003
Parameter copy
(35R5GB/37R5PB
or above)
0: No action
1: Parameters download
2: Parameters upload
3: Download parameters except
motors
Note: This function is only valid for
LCD keyboard.
0 ×
PF.04 G/P selection
0: Type G (Constant torque)
1: Type P (Inlet fan and pump series
loads)
0 × 1004