EasyManua.ls Logo

Alpha 6000 - P2: Auxiliary Operation

Alpha 6000
219 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4 Parameter Index
58
P2: Auxiliary Operation
Function
code
Function Name Range of settings Default Change
MODBUS
Address
P2.00 Jog frequency 0.10~Upper limit frequency 5.00Hz 0300
P2.01 Acc time of Jog
3132G/3160P or below:
0.1~3600s
3160G/3185P or above:
1.0~3600s
3022G/3030P
or below:
6.0s
3030G/3037P
or above:
20.0s
0301
P2.02 Dec time of Jog
3132G/3160P or below:
0.0(Free stopping)~3600s
3160G/3185P or above:
0(Free stopping), 1.0~3600s
0302
P2.03
Switching time
between run
forward and
reverse
0.0~3600s 0.0s 0303
P2.04
Frequency lower
limit deal mode
0: Running at frequency Lower
limit
1: Zero-speed running
0 × 0304
P2.05
Frequency
departure setting
0.00-2.50Hz 0.00Hz 0305
P2.06 Carrier frequency
This value depends on the
inverter model
This value
depends on
the inverter
model
× 0306
P2.07 Jump frequency 1 0.00~Max frequency 0.00Hz × 0307
P2.08 Jump frequency 2 0.00~Max frequency 0.00Hz × 0308
P2.09 Jump frequency 3 0.00~Max frequency 0.00Hz × 0309
P2.10
Jump frequency
bandwidth
0.00~15.00Hz 0.00Hz × 030A
P2.11
Multi-step
frequency 1
0.00~Maximum frequency
5.00 Hz
030B
P2.12
Multi-step
frequency 2
0.00Hz
030C
P2.13
Multi-step
frequency 3
030D
P2.14
Multi-step
frequency 4
030E
P2.15
Multi-step
frequency 5
030F
P2.16
Multi-step
frequency 6
0310
P2.17
Multi-step
frequency 7
0311
P2.18
Multi-step
frequency 8
0312
P2.19
Multi-step
frequency 9
0313

Table of Contents