Chapter 4 Parameter Index
58
P2: Auxiliary Operation
Function
code
Function Name Range of settings Default Change
MODBUS
Address
P2.00 Jog frequency 0.10~Upper limit frequency 5.00Hz ○ 0300
P2.01 Acc time of Jog
3132G/3160P or below:
0.1~3600s
3160G/3185P or above:
1.0~3600s
3022G/3030P
or below:
6.0s
3030G/3037P
or above:
20.0s
○ 0301
P2.02 Dec time of Jog
3132G/3160P or below:
0.0(Free stopping)~3600s
3160G/3185P or above:
0(Free stopping), 1.0~3600s
○ 0302
P2.03
Switching time
between run
forward and
reverse
0.0~3600s 0.0s ○ 0303
P2.04
Frequency lower
limit deal mode
0: Running at frequency Lower
limit
1: Zero-speed running
0 × 0304
P2.05
Frequency
departure setting
0.00-2.50Hz 0.00Hz ○ 0305
P2.06 Carrier frequency
This value depends on the
inverter model
This value
depends on
the inverter
model
× 0306
P2.07 Jump frequency 1 0.00~Max frequency 0.00Hz × 0307
P2.08 Jump frequency 2 0.00~Max frequency 0.00Hz × 0308
P2.09 Jump frequency 3 0.00~Max frequency 0.00Hz × 0309
P2.10
Jump frequency
bandwidth
0.00~15.00Hz 0.00Hz × 030A
P2.11
Multi-step
frequency 1
0.00~Maximum frequency
5.00 Hz
○
030B
P2.12
Multi-step
frequency 2
0.00Hz
030C
P2.13
Multi-step
frequency 3
030D
P2.14
Multi-step
frequency 4
030E
P2.15
Multi-step
frequency 5
030F
P2.16
Multi-step
frequency 6
0310
P2.17
Multi-step
frequency 7
0311
P2.18
Multi-step
frequency 8
0312
P2.19
Multi-step
frequency 9
0313