Appendix3 Main Circuit Output Cable Selection (Recommended)
197
Voltage
(V)
Power
grade(kW)
Wire
gauge(mm
2
)
The maximal length of output cable(m)
Without output
reactor
With output reactor
No
Shielded
Cable
( m)
Shielded
Cable
(m)
No
Shielded
Cable
(m)
Shielded
Cable
(m)
380
280kW 185*2 320 280 550 430
315kW 250*2 320 280 550 430
355kW 325*2 320 280 550 430
400kW 325*2 320 280 550 430
500kW 325*2 320 280 550 430