Chapter 4 Parameter Index
76
Function
code
Function Name Range of settings Default Change
MODBUS
Address
Pd.09
Input phase loss
detection delay
time
2~255s 10s × 0E09
Pd.10
Output phase loss
detection level
(SP0)
(Motor rated
current
corresponds to
100%)
0~100% 2% × 0E0A
Reserved
(S2R4GB,
S2R75GB)
Pd.11
Output phase loss
detection delay
time
0.0~25.0s 2.0s × 0E0B
Pd.12
Enabling
keyboard keys
UP/DN
0: Invalid
1: Enabled
0 × 0E0C
Pd.13
AE1, AE2 Alarm
choice
0: Not show alarm
1: Display alarm
0 × 0E0D
Pd.14 Auto reset times
0~10,"0"means “auto reset” is
disabled.
Only 3 faults have auto reset function
0 × 0E0E
Pd.15 Reset Interval 2.0~20.0s /per time 5.0s ×
0E0F
Pd.16
Increase and
decrease of
over-current
counting
0 ~ 250 100 × 0E10
Pd.17
Automatic
running selection
after power on
0:No action
1:Run automatically
1 × 0E11
Pd.18
Running selection
after power off
0:Machine shut down (through the
shutdown way)
1:Don’t stop(short time)
1 × 0E12
Pd.19
Resistance
coefficient to
impact load
100.0~250.0%
This
value
depends
on the
inverte
r model
× 0E13
Reserved(3004G/
35R5PB or
below)