CPS100 SERIES OPERATION MANUAL
SECTION 7:
Remote Control Programming
Entire Contents Copyright 2018 by Adaptive Power Systems, Inc. (APS) • All Rights Reserved • No reproduction without written authorization from APS.
APS CPS100 Series Power Source Operation Manual Page 158 of 231
Command Description
OUTPUT:IMPED:RES:_<nr2> Sets the Zo_R resistance of the output impedance. (Zo_R)
in ohms. Range is 0.01 ~ 1.00. Returns OK or FALSE.
OUTPUT:IMPED:RES? Queries the R setting of the output impedance (Zo_R) in
Ohms.
OUTPUT:IMPED:INDU:_<nr2> Sets the Zo_L inductance of the output impedance. (Zo_L)
in mH. Range is 0.01 ~ 1.00. Returns OK or FALSE.
OUTPUT:IMPED:INDU? Queries the L setting of the output impedance (Zo_L) in
mH.
OUTPUT:RANGE:_<nr2> Sets the output voltage range as follows:
<nr2> 0 150V
1 300V
2 AUTO
Return signal is OK or FALSE.
OUTPUT:RANGE? Queries the voltage range setting.
0 = 150V / 1 =300V / 2 = AUTO
OUTPUT:COUPLE:_<nr2> Sets the output coupling.
<nr2> 0 AC
1 DC
2 AC+DC
Return signal is OK or FALSE.
OUTPUT:COUPLE? Queries the output coupling setting.
0 = AC / 1 = DC / 2 = AC+DC
OUTPUT:IRANGE:_<nr2> Sets the current measurement range.
<nr2> 0 High Range
1 Middle Range
2 Low Range
3 mA Range
OUTPUT:IRANGE? Queries the current measurement range.
0 = High / 1 = Middle / 2 = Low / 3 = mA / 4 = Auto
OUTPUT:ISSTART:_<nr2> Sets the delay time for testing surge current Is in msec.
Range is 0 ~ 999. Returns OK or FALSE.
OUTPUT:ISSTART? Queries the delay time setting for the inrush current test.
OUTPUT:ISINTERVAL:_<nr2> Sets the interval time for testing surge current Is in msec.
Range is 0 ~ 999. Returns OK or FALSE.
OUTPUT:ISINTERVAL? Queries the interval time setting for the inrush current
test.
Table 7-7: OUTPUT Sub-system Commands