CPS100 SERIES OPERATION MANUAL
SECTION 8:
Master Slave Operation
Entire Contents Copyright 2018 by Adaptive Power Systems, Inc. (APS) • All Rights Reserved • No reproduction without written authorization from APS.
APS CPS100 Series Power Source Operation Manual Page 187 of 231
Multi-Unit Programming Instructions
Some front panel operations and menu operate differently when using multi-unit
configurations. The table below provides and overview of the key differences between
stand-alone mode (1 unit only) and any of the available multi-unit configurations.
Menu
Sub-Menu
Parallel
Series
3-Phase
Output
& More
Waveform Yes, Slaves in sync with the master unit
On Degree
Yes, Slaves in sync with the master unit
Applies to phase A
only. Phase B &C will
be shifted 120° & 240°
Off Degree
Yes, Slaves in sync with the master unit
Soft Start
1
Yes, Slaves in sync with the master unit
Coupling
Yes, Slaves in sync with the master unit
Range
Yes, Slaves in sync with the master unit
Waveform
Preview
Yes but only Master unit can display
Zo Program Not supported
Measure Setting
Irange
Yes, Slaves in sync with the master unit
Average
Yes
Yes
Yes
Is Delay
Yes
Yes
Yes
Is Interval
Yes
Yes
Yes
Waveform Viewer
Yes
Yes
Yes
Limitation
Yes, Slaves in sync with the master unit
Config
Remote Control
Yes
Yes
Yes
System Setting
2
Yes
Yes
Yes
External Control
Yes
Yes
Yes
Protection
Yes, Slaves in sync with the master unit
LCD Setting
Yes
Yes
Yes
Calibration
3
Not supported
Not supported
Not supported
Other
Yes
Yes
Yes
Output Mode
PLD Testing
Yes
Yes
Yes
Harmonics
4
Yes
Yes
Not supported
IEC Standard
5
Yes
Yes
Yes
Special Function Yes Yes Not supported
Test Mode
Not supported
Not supported
Not supported
Store / Recall
Yes
Yes
Yes
Table 8-1: Multi-Unit Programming Summary
Footnotes:
1. Soft Start includes Vac S/R, Vdc S/R and F S/R settings
2. O/P Relay function set as ON only available in single mode.
3. Calibration function only only available in single mode.
4. Harmonics function only available for the master unit.
5. Only IEC 61000-4-11 available for the 3-phase system.