Error information
Manual b maXX
®
BM1000
Document No. 5.07003.04 Baumüller Nürnberg GmbH
84
of 174
8.3
00A1
hex
cP10 Communication time-
out error on the control
board or power board
PWM
inhibit
m Press RESET key to set all parameters to
factory setting
m Return the b maXX
®
to the factory
00B0
hex
cF10
cF11
cF20
cF21
EEPROM error P1007
m cF10,cF11:
internal EEPROM can not be pro-
grammed (return the b maXX
®
to the fac-
tory)
m cF20,cF21:
internal EEPROM can not be read (set all
parameters to factory setting or return the
b
maXX
®
to the factory)
00B2
hex
Ecnt Checksum error in
EEPROM
PWM
inhibit
m The parameter (P0077, P0110, P0811,
P0812, P0850, P1172, P1173, P1176,
P1177, P1180, P1181, P1182, P1183,
P1184, P1361, P1362, P1363, P1359)
writing to the EEPROM by power off was
not completed.
0500
hex
oH1 IGBT Overheating PWM
inhibit
m Ensure that the ambient temperature is
within the specified temperature range.
m Make sure that the ventilation holes are
not obstructed.
m Remove any foreign objects from the
heatsink and check for possible dirty heat
sink fins.
m Check the fan and clean it.
m Provide enough spacing for adequate
ventilation.
0501
hex
Lv Low voltage
The device detects that
the DC link voltage has
fallen below its minimum
value.
P0297
m Check whether the input voltage falls
within the device rated input voltage
range.
m Check for abnormal load in motor.
m Check for correct wiring of input power
(for 3-phase models) without phase loss.
0502
hex
PHL Phase loss PWM
inhibit
m Check input phase wiring for loose con-
tacts
0503
hex
codE Password invalid P1007
m Return the b maXX
®
to the factory
Fault
code
Fault
name
Fault description Error
reaction
Corrective actions