20 en | Compliance Settings Control Panel
2017.03 | 09 | F.01U.303.998 Program Entry Guide Bosch Security Systems, Inc.
PANEL WIDE PARAMETERS > Report Routing > Fire Reports > Fire Cancel
Set the PANEL WIDE PARAMETERS > Report Routing > Fire Reports > Fire Cancel parameter
for each Route Group (1 to 4) to No.
Figure2.1: Fire Cancel
POINTS > Point Profiles (Point Indexes)
Configure Point Profiles 1, 4, and 6 as shown below.
It is important to configure the parameters in order.
Point Profile 1
Set Alarm Abort to: No.
Set Point Profile Text (First Language) to: Fire Panel Trouble.
Set PointType/Response/Circuit Style > PointType to: FirePoint.
Set PointType/Response/Circuit Style > Circuit Style to: SingleEOL(1KΩ) or
SingleEOL(2KΩ).
Set Response to: 3.
Point Profile 4
Set Point Profile Text (First Language) to: Fire Panel Alarm.
Set PointType/Response/Circuit Style > PointType to: FirePoint.
Set PointType/Response/Circuit Style > Circuit Style to: SingleEOL(1KΩ),
SingleEOL(2KΩ), or DualEOL.
If you set PointType/Response/Circuit Style > Circuit Style to SingleEOL(1KΩ) or
SingleEOL(2KΩ), set Response to: 1.
If you set Point Type / Response / Circuit Style > Circuit Style to DualEOL, set Response to: 0.
Point Profile 6
Set Point Profile Text (First Language) to: Fire Panel Supervisory.
Set PointType/Response/Circuit Style > PointType to: FirePoint.
Set PointType/Response/Circuit Style > Circuit Style to: SingleEOL(1KΩ),
SingleEOL(2KΩ), or DualEOL.