Control Panel Compliance Settings | en 25
Bosch Security Systems, Inc. Program Entry Guide 2017.03 | 09 | F.01U.303.998
Figure2.8: Point Profile 20
POINTS > Point Assignments
Set the POINTS > Point Assignments, Source, Text, and Profile parameters, for points 9, 10,
and 19 as follows.
Point 9
Set Point Assignments > Source to: Ouput.
Set Point Assignments > Text to: Fire Alarm Active.
Set Point Assignments > Profile to: 20 - CF: Silence
Point 10
Set Point Assignments > Source to: Ouput.
Set Point Assignments > Text to: Fire Trouble Active.
Set Point Assignments > Profile to: 20 - CF: Silence
Point 19
Set Point Assignments > Source to: Ouput.
Set Point Assignments > Text to: Fire Supervisory Active.
Set Point Assignments > Profile to: 20 - CF: Silence