THS – FI022GB2K8v3 --- V - MAINTENANCE
70
Remote Possible settings Standard setting Parameter
No code eject
NE
ON / OFF OFF
Global
Description Models
Ejection of packs with wrong code
When activated, the packages without barcodes or with invalid barcodes are ejected. If deactivated, there is no
action. This command is available only if the barcode reader function is enabled.
Note: In order to function, a photocell for synchronisation of the packs must be installed.
This photocell can be installed before or after the THS probe; HOWEVER, IT MUST BE
INSTALLED AFTER THE BARCODE READER
All models,
except THS/G
THS Configuration menu
Remote Possible settings Standard setting Parameter
Line ID
ID
1000 - 9999 9999
Global
Description Models
ID of individual metal detector in network of devices linked via RS485
When connected via RS485, on each metal detector must be set a different value of ID. Maximum of units: 32.
All models
Remote Possible settings Standard setting Parameter
Operator access
OA
ON / OFF ON
Global
Description Models
Operator access to sensitivity setting
If OA is set to ON the operator can change the sensitivity.
All models
Remote Possible settings Standard setting Parameter
Sound
SO
ON / OFF ON
Global
Description Models
Activation of the built-in buzzer
All models
Remote Possible settings Standard setting Parameter
TP follower
FO
ON / OFF OFF
Global
Description Models
Automatic adjustment of variations in the characteristics of the product
If activated, in case of product with chemical-physical characteristics which can vary gradually with time, the detector
automatically determines the best point of operation and varies the TP parameter accordingly.
All models,
except THS/MN
Remote Possible settings Standard setting Parameter
Language
LG
See below -
Global
Description Models
Language for messages
THSVxxxa GB / D / F / I
THSVxxxb GB / D / NL / S
THSVxxxc GB / P / E / JP
The last character of the software versione indicates the group of
selectable languages, following the table beside, where the
International Codes are used to identify each language.
THSVxxxd GB / D / F / H
All models
Remote Possible settings Standard setting Parameter
Inhib. time
IN
0 – 3000
hundredths of a second
0
Global
Description Models
Inhibition time
Inibiths the metal detector alarm for a certain time.
If KT=0.000 (MDL or MDT not fitted), the time refers to the activation of the “Inhibition input”. If KT
≠
0.000, the time
refers to the conveyor startup.
All models